The available capacity of the backup heater is determined based on the Voltage
setting:
[5-0D]
0: 230V, 1ph 3 kW
2: 400V, 3ph 6 kW
4
See "Emergency"  [
  196] for more information about Emergency operation and
Compressor forced off mode.
Equilibrium
#
Code
[9.3.6]
[5-00]
[9.3.7]
[5-01]
Operation
#
Code
[9.3.8]
[4‑00]
INFORMATION
When heating of the DHW by the heat pump is too slow, it may affect a comfortable
operation of the space heating/cooling circuit. If so, allow the backup heater to assist
during DHW operation by setting [4-00]=1 or 2.
Maximum capacity
During normal operation the maximum capacity is:
3 kW for a 230 V, 1N~ unit
6 kW for a 400 V, 3N~ unit
The maximum capacity of the backup heater can be limited. The set value depends
on the used voltage (see table below) and is then the maximum capacity during
emergency operation.
#
Code
(a)
[9.3.5]
[4-07]
Normal operation
Equilibrium: Deactivate backup heater (or
external backup heat source in case of a bivalent
system) above the equilibrium temperature for
space heating?
0: No
1: Yes
Equilibrium temperature: Outdoor
temperature below which operation of the
backup heater (or external backup heat source in
case of a bivalent system) is allowed.
Range: –15°C~35°C
Backup heater operation:
0: Restricted
1: Allowed
2: Only
DHW: Backup heater operation is
enabled for domestic hot water and disabled
for space heating.
0~6 kW when voltage is set to 230 V, 1N~
0~9 kW when voltage is set to 400 V, 3N~
11
Configuration
|
Emergency or Compressor
forced off
6 kW
9 kW
Description
Description
Description
Installer reference guide