Wiring Topic - Eaton ESR5-NO-31-24VDC Manual

Emergency-stop and protective door monitoring
Table of Contents

Advertisement

3.4.2 Wiring topic

Connect the cables to the connection terminals with the help of a screw-
driver.
B
A
Figure 13:
Connection of the cables
Ferrules are recommended when connecting flexible cables.
Use copper wire approved for temperatures of up to 60 °C /
75 °C in order to meet the requirements for the UL listing.
Apply the nominal input voltage U
The Power LED is lit.
Connect the contacts S11/S12 and S21/S22.
→ The IN 1/2 LED is lit.
Automatic start
→ The signal current path 41/42 opens.
→ The enable current paths 13/14, 23/24 and 33/34 close.
→ The K1 and K2 LEDs are lit.
ESR5-NO-31-24VDC 11/23 MN049018EN Eaton.com
AWG 24-12
2
0.2 - 2.5 mm
7 mm (0.28")
0.5 - 0.6 Nm
(5 - 7 lb-in)
(24 V DC) to terminals A1/A2. →