Derating; Use At Altitudes Greater Than 2000 M Above Sea Level. Nn - Eaton ESR5-NO-31-24VDC Manual

Emergency-stop and protective door monitoring
Table of Contents

Advertisement

1 Description ESR5-NO-31-24VDC

1.13 Derating

1.13.1 Use at altitudes greater than 2000 m above sea level. NN

13
The derating curves apply under the following conditions:
Mounting on vertical or horizontal mounting rail
Devices mounted without distance to each other
with U
up to max. 26.4 V DC
N
I
² = I
² + I
² + I
max
1
2
Horizontal mounting position
Figure 4:
Derating curve – horizontal mounting positions, without distance
Vertical mounting position
Figure 5:
Derating curve – vertical mounting positions, without distance
The following section describes the special conditions for the
use of an ESR5-NO-31-24VDC at altitudes greater than
2000 m abovesea level.
Make sure to observe the corresponding device-specific specifi-
cations (technical data, derating, etc.).
The use of the device ESR5-NO-31-24VDC at altitudes higher than 2000 m
above sea leveland up to a maximum of 4500 mabove sea level is
allowed provided that:
1.
Rated input voltage V
2.
The maximum switching voltage at the relay outputs for enable current
paths 13/14, 23/24, 33/34, 43/44: min. 10 V, max. 250 VAC
and signal current path 51/52: min 5 V, max. 250 VAC is not exceeded
▶ 1.Reduce the maximum ambient temperature for operation by the corre-
sponding temperature derating factor as per the following table.
ESR5-NO-31-24VDC 11/23 MN049018EN Eaton.com
²
3
: 24 VDC (-15%/+10%) is maintained and
N
.