1 Description ESR5-NE-51-24VDC

1.13 Derating

1.13.1 Use at altitudes greater than 2000 m above sea level. NN

13
The derating curve applies under the following conditions:
Mounting on vertical or horizontal mounting rail
Devices mounted without distance to each other
with U
up to max. 26.4 V DC (24 V -20%/+10%)
N
I
² = I
² + I
² + I
max
1
2
80
72
70
60
50
40
32
30
20
10
0
0
10
20
30
Figure 4:
Derating curve – vertical and horizontal mounting positions, without distance
The following section describes the special conditions for the
use of an ESR5-NE-51-24VDC at altitudes greater than
2000 m abovesea level.
Make sure to observe the corresponding device-specific specifi-
cations (technical data, derating, etc.).
The use of the device ESR5-NE-51-24VDC at altitudes higher than 2000 m
above sea leveland up to a maximum of 4500 mabove sea level is
allowed provided that:
1.
Rated input voltage V
The maximum switching voltage at the relay outputs for 
2.
enable current paths 33/34, 43/44, 53/54, 63/64 and the 
feedback current path 11/12: min. 10 V, max. 250 VAC
and signal current path 71/72: min 5 V, max. 250 VAC 
is not exceeded
.
▶ 1.Reduce the maximum ambient temperature for operation by the corre-
sponding temperature derating factor as per the following table.
Altitude above sea
Temperatur-Derating-Factor
level
2000 m
1
2500 m
0.953
3000 m
0.906
3500 m
0.859
4000 m
0.813
4500 m
0.766
ESR5-NE-51-24VDC 11/23 MN049019EN Eaton.com