5 Configuration
#
Code
[A.2.2.5]
[C-06]
External room thermostat for the
additional zone:
▪ 0: N/A
▪ 1 (Thermo ON/OFF): When the used
external
heat pump convector can only send a
thermo ON/OFF condition.
▪ 2 (H/C request): Because only heating
is possible, the used external room
thermostat can only send a thermo
ON/OFF condition.
[A.2.2.B]
[C-08]
External sensor:
▪ 0 (No): NOT installed.
▪ 1 (Outdoor sensor): Connected to
PCB
temperature.
▪ 2 (Room sensor): Connected to PCB
measuring the indoor temperature.
Digital I/O PCB
#
Code
[A.2.2.6.1]
[C-02]
External backup heater source:
▪ 0 (No): None
▪ 1 (Bivalent): Gas, oil boiler
▪ 2: N/A
▪ 3: N/A
[A.2.2.6.2]
[D-07]
Solar pump station kit:
▪ 0 (No): NOT installed
▪ 1 (Yes): Installed
[A.2.2.6.3]
[C-09]
Alarm output on optional EKRP1HB
PCB:
▪ 0 (Normally open): The alarm output
will be powered when an alarm
occurs. By setting this value, a
distinction is made between the
detection of an alarm, and the
detection of a power failure.
▪ 1 (Normally closed): The alarm
output will NOT be powered when an
alarm occurs.
See also table below (Alarm output
logic).
[A.2.2.6.4]
[F-04]
Bottom plate heater
▪ 0 (No): NOT installed
▪ 1 (Yes): Installed
Alarm output logic
[C-09]
Alarm
0 (default)
Closed output
1
Open output
Installation manual
14
Description
room
thermostat
or
measuring
the
outdoor
Description
No alarm
No power
supply to unit
Open output
Open output
Closed output
Demand PCB
#
Code
[A.2.2.7]
[D-04]
Demand PCB
Only applicable for EHVH04+08.
Indicates if the optional demand PCB is
installed.
▪ 0 (No)
▪ 1 (Pwr consmp ctrl)
Energy metering
#
Code
[A.2.2.8]
[D‑08]
Optional external kWh meter 1:
▪ 0 (No): NOT installed
▪ 1: Installed (0.1 pulse/kWh)
▪ 2: Installed (1 pulse/kWh)
▪ 3: Installed (10 pulse/kWh)
▪ 4: Installed (100 pulse/kWh)
▪ 5: Installed (1000 pulse/kWh)
[A.2.2.9]
[D‑09]
Optional external kWh meter 2:
▪ 0 (No): NOT installed
▪ 1: Installed (0.1 pulse/kWh)
▪ 2: Installed (1 pulse/kWh)
▪ 3: Installed (10 pulse/kWh)
▪ 4: Installed (100 pulse/kWh)
▪ 5: Installed (1000 pulse/kWh)
5.2.4
Quick wizard: Capacities (energy
metering)
#
Code
[A.2.3.1]
[6-02]
Anti-legionella heater capacity [kW]
[A.2.3.6]
[6-07]
Bottom plate heater capacity [W]
5.2.5

Space heating control

Leaving water temperature: Main zone
#
Code
[A.3.1.1.1]
N/A
Set point mode:
▪ 0 (Fixed): Absolute
▪ 1
dependent
▪ 2
scheduled (only for leaving water
temperature control)
▪ 3
dependent + scheduled (only for
leaving water temperature control)
EHVH04+08S18CBV + EHVH08~16S26CBV
Description
Description
Description
Description
(Weather
dep.):
Weather-
(Fixed/scheduled):
Absolute
(WD/scheduled):
Weather-
Daikin Altherma – Low temperature split
4P449977-1B – 2018.02
+