Domestic Hot Water Control: Advanced - Daikin Altherma EHVH/X16S18+26CA Installer's Reference Manual

Low temperature split
Table of Contents

Advertisement

8 Configuration
#
Code
[A.3.1.1.6.1] [F-0B]
The shut-off valve:
0 (No)(default): is NOT influenced by
heating or cooling demand.
1 (Yes): closes when there is NO heating
or cooling demand.
INFORMATION
The setting [F‑0B] is only valid when there is a thermostat
or external room thermostat request setting (NOT in case
of leaving water temperature setting).
Cooling: Only applicable for EHBX and EHVX. The shut-off valve
closes, depending on [F-0C] when the unit is running in cooling
operation mode. Enable this setting to avoid cold leaving water
through the heat emitter and the forming of condensation (e.g. under
floor heating loops or radiators).
#
Code
[A.3.1.1.6.2] [F-0C]
The shut-off valve:
0 (No): is NOT influenced by changing
the space operation mode to cooling.
1 (Yes)(default): closes when the space
operation mode is cooling.
Operation range
Depending on the average outdoor temperature, the operation of the
unit in space heating or space cooling is prohibited.
Space heating OFF temp: When the averaged outdoor temperature
raises above this value, space heating is turned OFF to avoid
overheating.
#
Code
[A.3.3.1]
[4-02]
▪ EHBH/X04+08
14~25°C (default: 25°C)
▪ EHBH/X16 and EHVH/X16: 14~35°C
(default: 35°C)
The same setting is also used in
automatic heating/cooling changeover.
Space cooling On temp: Only applicable for EHBX and EHVX. When
the averaged outdoor temperature drops below this value, space
ooling is turned OFF.
#
Code
[A.3.3.2]
[F-01]
10~35°C (default: 20°C)
The same setting is also used in
automatic heating/cooling changeover.
Automatic heating/cooling changeover
Only applicable for EHBX and EHVX. The end-user sets the
desired operation mode on the user interface: Heating, Cooling or
Automatic (see also operation manual/user reference guide). When
Automatic is selected, the changing of the operation mode is based
on:
▪ Monthly allowance for heating and/or cooling: the end-user
indicates on a monthly base which operation is allowed (# [7:5]):
both heating/cooling or heating only or cooling only. If the allowed
operation mode changes to cooling only, the operation mode
changes to cooling. If the allowed operation mode changes to
heating only, the operation mode changes to heating.
▪ Averaged outdoor temperature: the operation mode will be
changed in order to always be within range determined by the
space heating OFF temperature for heating and the space cooling
On temperature for cooling. If the outdoor temperature drops, the
operation mode switches to heating and vice versa. Note that the
outdoor temperature will be time-averaged (see "8 Configuration"
on page 33).
Installer reference guide
46
Description
Description
Description
and
EHVH/X04+08:
Description
When the outdoor temperature is between the space cooling On and
the space heating OFF temperature, the operation mode remains
unchanged unless the system is configured in room thermostat
control with one leaving water temperature zone and quick heat
emitters. In that case, the operation mode will change based on:
▪ Measured indoor temperature: besides the heating and the
cooling desired room temperature, the installer sets a hysteresis
value (e.g. when in heating, this value is related to the desired
cooling temperature) and an offset value (e.g. when in heating,
this value is related to the desired heating temperature). Example:
the desired room temperature in heating is 22°C and in cooling
24°C, with a hysteresis value of 1°C and an offset of 4°C.
Changeover from heating to cooling will occur when the room
temperature raises above the maximum of the desired cooling
temperature added by the hysteresis value (thus 25°C) and the
desired heating temperature added by the offset value (thus
26°C). Oppositely, changeover from cooling to heating will occur
when the room temperature drops below the minimum of the
desired heating temperature subtracted by the hysteresis value
(thus 21°C) and the desired cooling temperature subtracted by the
offset value (thus 20°C).
▪ Guard timer to prevent too frequent changing from heating to
cooling and vice versa.
Changeover settings related to the outdoor temperature (only when
automatic is selected):
#
Code
[A.3.3.1]
[4-02]
Space heating OFF temp. If the outdoor
temperature raises above this value, the
operation mode will change to cooling:
▪ EHBH/X04+08
14~25°C (default: 25°C)
▪ EHBH/X16 and EHVH/X16: 14~35°C
(default: 35°C)
[A.3.3.2]
[F-01]
Space cooling On temp. If the outdoor
temperature drops below this value, the
operation mode will change to heating:
10~35°C (default: 20°C)
Changeover settings related to the indoor temperature. Only
applicable when Automatic is selected and the system is configured
in room thermostat control with 1 leaving water temperature zone
and quick heat emitters.
N/A
[4-0B]
Hysteresis: Ensures that changeover is
only done when necessary. Example: the
space operation mode only changes
from cooling to heating when the room
temperature drops below the desired
heating temperature subtracted by the
hysteresis.
1~10°C, step 0.5°C (default: 1°C)
N/A
[4-0D]
Offset: Ensures that the active desired
room temperature can be reached.
Example: if heating to cooling
changeover would occur below the
desired room temperature in heating, this
desired room temperature could never
be reached.
1~10°C, step 0.5°C (default: 1°C)
8.3.2

Domestic hot water control: advanced

Preset tank temperatures
Only applicable when domestic hot water preparation is scheduled
or scheduled + reheat.
You can define preset tank temperatures:
▪ storage economic
▪ storage comfort
ERHQ011~016BA + ERLQ011~016CA + EHVH/X16S18+26CA
Description
and
EHVH/X04+08:
Daikin Altherma - Low Temperature Split
4P313777-1C – 2012.11