Bst Setup: Constant Setpoint; Bst Setup: Remote Setpoint - Watts AERCO Edge CFR 3000 Operator's And Service Manual

Boiler with edge controller, natural gas modulating boilers
Hide thumbs Also See for AERCO Edge CFR 3000:
Table of Contents

Advertisement

SECTION 7 BOILER SEQUENCING TECHNOLOGY

7.2.1 BST Setup: Constant Setpoint

Complete the instructions below to configure the Controller for Constant Setpoint.
On All Boilers:
Main Menu → Advanced Setup → BST Cascade → Cascade Configuration
1. Go to:
Mode parameter to BST Client.
Main Menu → Advanced Setup → BST Cascade → Cascade Communication
2. Go to:
Address parameter to the communication address of the unit.
On the BST Manager only:
Main Menu → Advanced Setup → BST
1. Go to
menu in the table below.
Menu/Screen
Name
Auto Manager Transfer
Backup Manager Address
Cascade
Unit Mode
Configuration
Hdr Temp Sensor
Sensor Comm Address
Hdr Temp Point
Application
Application
SH Operating Mode
Configuration
Plant Setpoint
Min address
Cascade Comm
Max address
Cascade Baud Rate

7.2.2 BST Setup: Remote Setpoint

Complete the instructions below to configure the Controller for Remote Setpoint.
On All Boilers:
Main Menu → Advanced Setup → BST Cascade → Cascade
1. Go to:
Main Menu → Advanced Setup → BST Cascade → Cascade
2. Go to:
On the BST Manager only:
Main Menu → Advanced Setup → BST
1. Go to
menu in the table below.
Parameters
Set the Unit Mode parameter to BST Client.
Set the Unit Address parameter to the communication address of the
unit.
Cascade, set the Parameters to the Values in each
Values
Enabled (This is available on the Manager unit
only)
Enter the designated backup unit address
BST Manager
Network
240
14
Space Heating
Constant Setpoint
Header temperature required for the cascade
The minimum unit address in the cascade
The maximum unit address in the cascade
The baud rate for the cascade.
Cascade, set the Parameters to the Values in each
and set the Unit
and set the Unit
Configuration:
Communication: