SECTION 8 MAINTENANCE
Figure 8-3: External Condensate Trap
If your system includes a condensate neutralizer, the active ingredient must be replaced periodically.
8.7 Air Filter Cleaning and Replacement
The boiler's air filter should be cleaned every 12 months; it should be replaced after 24 months if it shows
any signs of deterioration. However, if it is still in good condition, you can order a 24 Month Maintenance
kit that includes an air filter cleaning kit in place of a new filter.
NOTE: Failure to clean or replace the air filter may hinder unit efficiency and combustion reliability.
All 24 Month Maintenance Kits include one of two parts:
•
An Air Filter Cleaning Kit – Appropriate if the filter is intact
•
New Air Filter – Necessary if the filter is deteriorated or damaged
Check Table 8-2b, above, to find the part number of the kit appropriate for your site. Instructions are
included in the TID that accompanies the kit.
•
Figure 8-4: Condensate Trap and Neutralizer
•
–
Cross-Section & Exploded View
•