Benchmark 750 – 1000 Boiler User Manual - INTERNATIONAL

3.9 BST (Boiler Sequencing Technology) Menu

The BST menu must be enabled in order to be displayed and accessed. The BST Menu item,
located at the end of the Configuration menu (item 32 in Table 3-4), must be se to Enabled.
The BST menu contains all of the items required to configure, operate and monitor the
functionality of the BST System. There are over 50 items in this menu, and selecting any
particular item from the list, for inspection or modification, could be time consuming. As a result,
the BST menu has been segmented into FIVE logical groups based on functionality.
The five Item groups are:
1. BST Monitor Items
2. *BST SETUP MENU*
3. *OPERATE MENU*
4. *TEMP CTRL MENU*
5. *BST COMM MENU*
These displayed item groups are displayed in UPPER CASE letters, and are bounded by an
asterisk * in order to readily identify them within the item list.
The Items contained in group 1 (BST Monitor Items) are always displayed within the menu, as
these items are critical for proper system operation. Therefore, the BST Monitor Items Header
itself is not displayed.
The Items contained in groups 2-5 are not displayed unless that particular item group has been
enabled from the C-More keypad.
Menu Item Display
1
BST Mode
2
BST Setpoint
3
Header Temp
4
BST Fire Rate
5
BST Ave Fire Rate
6
BST Outdoor Temp
7
Units Available
8
Units Ignited
9
BST Valve State
10
1 Comm Errors 8
11
1 BST Units 8
12
*BST SETUP MENU*
13
BST Setpoint Mode
14
Head Temp Source
15
Header Temp Addr
Page 46 of 170
11/03/2016
CHAPTER 3 – OPERATION
Table 3-7: BST Menu
Available Choices or Limits
Minimum
Off
BST Setpt Lo Limit
Read Only – current Header temperature in °F
0
0
Read Only – current outdoor temperature in °F
0
0
0 (CLOSED)
0
0 (see table)
Disabled
Constant Setpoint
Network
0
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
Ph.: 800-526-0288
Maximum
BST Slave
BST Master
BST Setpt Hi Limit
100%
100%
8
8
1 (OPEN)
9
0 (see table)
Enabled
Remote
Outdoor
Setpoint
Reset
FFWD Temp
255
Default
Off
130°F (54.4°C)
N/A
Fire rate %
Avg Fire Rate %
N/A
Units Present
Units firing
0
0
0
Disabled
Constant Setpt
FFWD Temp
240
OMM-0119_0A