WARNING
:
If at
any
time during the
start-up
or operation of the
TURBOFIRE®
II,
excessive noise or vibration
is
noticed. turn the burner off immediately.
Serious injury can
result.
WARNING
:
Your TURBOFIAE®
II
is
designed
to
operate at
low excess air
without
producing smoke or soot. The smoke spot number should never exceed a
Number
2.
A
smoke spot number
greater
than the
Number
2
indicates
a.n
UNSAFE
burner
operation
14.
Allow
the burner/boiler to "warm up".
15.
Adjust
the
oil pump
pressure, oil
value
position
and/or linkage
rod length
to maintain
between 3 a11d 7% excess oxygen and the the (by-pass)
pressure
value
indicated in
the fire
test
report.
16.
Slowly
rotate
the
manual potentiometer knob
in small increments
to
the FULL OPEN
position.
Note
oxygen concentrations as
the burner
modulates.
The burner is now at HIGH
FIRE.
17.
Note excess oxygen concentrations
,
by
pass pressure
and
Bacharach smoke spot
number.
18.
Adjust
the oil pump pressure, orl valve position and/or
linkage
rod length to
maintai
n
between
3 and 7% excess oxygen and
the
by pass oil
pressure
indicated in
the fire
test
report
without
the burner producing a smoke spot number greater than Number 2.
19.
Turn the manual potentiometer
to
the CLOSED
position
noting
the
excess oxygen
concentrations as
the
burner modulates.
20.
Adjust
linkage
to
maintain between
3
and 7%
excess
oxygen at
all
firing rates between
high
and
low
fire.
21.
Check and verify that all
burner/boiler
safety controls are set correctly and operating
properly.
22.
Place
the
boiler
in AUTOMATIC mode.
Your
TURBOFIRE® II is now
ready to
go on-line.
Monitor the
burner/boiler for the
first
several
hours
while it
is operating
in
the AUTOMATIC mode
to
assure
safe, proper
operation.
Monitor
and
note
excess
oxygen and stack temperature, oil
(by
pass)
pressure.
23.
Fill
out
STAAT-UP
forms
24.
Instruct Maintenance
Personnel.
2 2
TuxboFire®
II
Burner

Advertisement

loading

Related Products for AESYS TurboFire II