14.
Screw
washers
and
brass
nuts
onto the
boiler
studs.
15.
Lower the lifting device so that
the studs support
the burner and
remove the
sling from
around
the
burner.
16.
Tighten the brass nuts on the studs
evenly
to
seal
the burner to the
boiler.
CAUTION:
Failure to tighten the brass nuts may result in a combustion
gas leak and
burner
overheating.
17.
Connect main gas line to
gas
train
connection on TurboFire® II.
See
Figure
8
"Retrofit
Gas Train
(Main)".
18.
Have an
electrical
contractor connect all electrical connections to
the gas train and
boiler
safety
and
control
switches
from the
control
panel provided
with
the
burner
exactly as
shown
in
the provided wiring diagram.
19.
Connect oil (and steam)
supply
to
the
burner.
1 0
GAS LINE
CONNECTION
COON
(FIELD)
CHARACTERIZED
GAS VALVE
LOW
PRESSURE
CUT OUT SWITCH
Figure
8.
Retrofit Gas Train
(Main)
Turbo
Fire® II
Burner
HIGH PRESSURE
CUT OUT SWITCH
GAS
VALVE