7. Test operation method (SkyAir only)

* In the case of VRV, see the manual attached to the outdoor unit.
Also see the installation manuals attached to the indoor unit and the
outdoor unit.
● Check that the wiring of the indoor unit and the outdoor unit is completed.
● Check that the switchbox cover of the indoor unit and the outdoor unit is closed.
● After refrigerant piping, drain piping and electric wiring are completed, clean the inside of the indoor
unit and the decorative panel.
● Perform the test operation according to the following procedure.
NOTE
● The backlight will be lit for approximately 30 seconds when pressing one of the operation
buttons.
● Operate the buttons only when the backlight is lit. However, the On/Off button can be operated
when the backlight is not lit.
7-1
Make sure to turn on the power at
least 6 hours before starting test
operation to protect the compressor.
7-2
Confirm that both the liquid and gas
stop valves are opened.
NOTE
After the air purge of the vacuum pump, the refrigerant pressure may not rise even
though the stop valve is opened. The reason is that the refrigerant system of the outdoor
unit is blocked by the electrical expansion valve or the like. Operation is no problem.
7-3
Set the operation mode to cooling by
using the Operation Mode Selector
button.
7-4
Press and hold the Cancel button for
4 seconds or longer. The Service
Settings menu is displayed.
BRC1E53
4P419250-1
2015.10
Test operation method (SkyAir only)
CAUTION
Make sure that the outer panel
and piping cover are closed
before operation (danger of
electric shock).
<Basic screen>
7-3
7-4
Cool
Set to
28
<Service Settings>
Press and hold the Cancel
°C
button for 4 seconds or
longer while the backlight
is lit.
Installer reference guide
18