Daikin BRC1E53 Installer's Reference Manual page 18

Wired remote controller
Hide thumbs Also See for BRC1E53:
Table of Contents

Advertisement

Field settings
Mode
FIRST
No.
CODE
(Note
NO.
1)
Filter Contamination -
Heavy/Light Setting for
when "Time to clean the
air filter" icon is shown
0
(when filter contamination
is heavy the time to clean
the air filter is to be
halved).
10 (20)
Long-life filter type (setting of the filter
sign indication time).
1
(Change setting when a ultra-long
filter is installed).
Thermostat sensor in the remote
2
controller.
Setting for when the filter sign is not to
3
be displayed.
Number of connected SkyAir
simultaneous operation indoor units
11 (21)
0
(setting for simultaneous operation
system).
External On/Off input from outside
1
(setting for when forced On/Off is to
be operated from somewhere else).
12 (22)
Thermostat differential changeover
2
(setting for when using a remote
sensor).
High air outlet velocity (for high ceiling
0
applications).
Selection of airflow direction (setting
1
for when a kit has been installed that
blocks the airflow).
Selection of airflow function (setting
3
for when using a decoration panel at
13 (23)
the outlet).
4
Airflow direction range setting.
The external static pressure setting
(setting according to the connected
duct resistance).
6
FHYK: follow the high ceiling setting.
Drain pump operation with
15 (25)
3
humidifying.
Thermostat sensor used for the "Auto"
operation mode and the Setback
1c
1
function (room temperature on
detailed display).
1c
12
External input B1.
1c
13
External input B2.
1e
2
Setback function.
1e
7
Rotation overlap time.
Installer reference guide
17
Description of the setting
Ultra long
life filter
Long life
filter
Standard
filter
SECOND CODE NO. (Note 2)
01
±10.000 hrs.
±5.000 hrs.
±2.500 hrs.
± 1.250 hrs.
±200 hrs.
± 100 hrs.
Ultra-long life
Long-life filter
Use combined
(with indoor
Do not use
thermistor)
Display
Do not display
Pair
Twin
On/Off
Forced OFF
operation
1°C
0.5°C
2.7 m < h
h ≤ 2.7 m
≤ 3.0 m
4-way flow
3-way flow
Equipped
Not equipped
Upper
Normal
High static
Normal
pressure
Normal
High ceiling
Equipped
Not equipped
Indoor thermistor
Remote
(intake
controller
temperature)
thermistor
Do not use
Do not use
Do not use
Heat only
30 minutes
15 minutes
02
03
filter
Use
exclusively
Triple
Emergency
3.0 m < h
≤ 3.5 m
2-way flow
Lower
Low static
pressure
Use
Use
Cool only
10 minutes 5 minutes
4P419250-1 – 2015.10
04
Double
twin
Forced
OFF
Cool and
Heat
BRC1E53