Press and hold the Cancel button for
4 seconds or longer in the Basic
screen. The Service Settings menu is
displayed.
7-11
Select
Test Operation
Settings menu and press the Menu/
Enter button. The Basic screen
returns and normal operation is
possible.
7-12
Check the functions according to the
operation manual.
7-13
When the decoration panel is not
installed, turn off the power after test
operation finishes.
CAUTION
● If the interior work is not completed when the test operation is finished, explain to the customer
that he should not operate the unit until the interior work is completed in order to protect the
indoor unit.
● (If the indoor unit is operated, the indoor unit may be contaminated with the materials which
arise from paints or adhesives during the interior work and water splash or water leak may
occur.)
CAUTION
● If it is not possible to operate the unit due to any malfunction, refer to
Malfunction diagnosis method .
● When the test operation finishes, check that the error code history is not displayed in the
Maintenance Information screen according to the following procedure.
7-14
Press the Menu/Enter button in the
Basic screen. The Main menu is
displayed.
BRC1E53
4P419250-1
2015.10
7-10
7-11
in the Service
7-14
Test operation method (SkyAir only)
Cool
Return
Setting
<Service Settings menu>
Service Settings
1/3
Test Operation
Maintenance Contact
Field Settings
Demand
Min Setpoints Differential
External Input Interlock
Return
Setting
<Basic screen>
NOTE
Test operation will automatically finish
after 30 minutes.
<Basic screen>
Cool
Set to
28
°C
<Main menu>
Press and hold the Cancel
button for 4 seconds or
longer while the backlight
is lit.
Press the Menu/Enter
button.
Press the Menu/Enter
button.
Installer reference guide
20