10. FIELD SETTING

10.3 ESP setting (Duct type only)

The static pressure can be freely adjusted by using specific wire remote controller.
Note: The pressure loss of filter is not included in the ESP data above.
LCD
C-Series wired controller
ESP setting (C-Series wired controller):
1
Press and hold "MODE" button and "ADD.FUNC." button for 3 seconds, symbol
starts blinking at the same time.
2
Press" / "button to adjust parameter number until "17" is displayed, and press "ENTER" button to enter
system parameter adaption state, symbol
3
Select desired parameter code 10 by pressing " / " button, and press "ENTER" button to confirm.
4
Select desired function code to rewrite the parameter values by pressing " /
"ENTER" button to confirm.
5
Press "ON/OFF" button or "CANCEL"button to quit.
ESP setting (E-Series wired controller):
If you still have any trouble, please contact local technical service center of our company for further information.
Model
The range of
( Btu/h)
ESP
9K
0-30Pa
12K/18K
0-50Pa
24K
0-40Pa
Error Indicator
Parameter
Code
Function Code
Function code set
0-30, function code value equals
static pressure value
[default: 10 (10Pa)]
0-50, function code value equals
static pressure value
[default: 35 (35Pa)]
0-40, function code value equals
static pressure value
[default: 40 (40Pa)]
stops blinking.