5-3. Special Function Instruction 6. Electrical Characteristics 6-1. Print Circuit Board (Indoor & Outdoor) 6-2. Fan Motor 6-3. Temperature Sensor 6-4. Compressor 6-5. Electric Reactor 6-6.Room Card Control, Fire Protection, ON/OFF Function 6-6-1.Instructions for the function setting of room card control, fire protection, ON/OFF function. 6-6-2.Instructions for the function setting of room card control, fire protection, ON/OFF function.
Page 4
The manufacturer shall in no way be responsible for improper installation or maintenance service, including failure to follow the instructions in this document. SPECIAL PRECAUTIONS When Wiring ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM. ●...
NOTE: The figure、size and parameter of the product may not be identical with the service manual, please take the actual product as the standard. 2. Product Specifications Note: “ ** ” mean code of Front Panel(See in 3-1 .Product Pictures). AS-18UR4SXA** AS-09UR4SVD**9 AS-12UR4SVE**9...
Page 6
Heating Setting Temperature 16-30 16-30 Range ℃ Cooling Operating 19-43 19-43 16-30 Temperature Range ℃ Heating Operating -10-43 -7-24 -7-32 Temperature Range ℃ Features Display on Front Panel LCD Wireless Remote Controller Removable and washable Panel Washable PP Filter 24 Hours Timer 3 Speed and Auto Indoor Fan Control Vertical Auto Swing Louver Manual Adjustable Horizontal Swing...
Page 7
3.21 3.21 EER for Cooling 3.21 3.41 COP for Heating 3.42 阿根廷A级 A级 Energy Class Cooling B级 阿根廷B级 Energy Class Heating R410A Refrigerant R410A R410A Refrigerant charge 1340 volume (5M) Additional ref. Volume High(dB (A)) Indoor Unit Noise Level Mid(dB (A)) Low(dB (A)) Outdoor Unit Noise Level...
Page 8
Indoor Unit Net Weight (Kg) Outdoor Unit Indoor Unit Packing Dimensions WxHxD (mm) Outdoor 830*315*530 940*385*630 830×315×530 Unit Indoor Unit Gross Weight (Kg) Outdoor Unit AS-30UR4SDK**00 AS-24UR4SDB**9 Model No. T1, H/P, INVERTER T1, H/P, INVERTER Type Ratings 7000 8800 Cooling Capacity 7300 8800 Heating Capacity...
Page 9
System Compressor Rotary Rotary Compressor type ATL232UDPC9AUL ATL232UDPC9AUL Compressor Model No. HIGHLY HIGHLY Compressor MFG Connecting Pipe Diameter Liquid Pipe inch Gas Pipe inch Cooling Setting Temperature 8-32 8-32 Range ℃ Heating Setting Temperature 8-32 8-32 Range ℃...
3. Product Picture and Drawing 3-1. Product Pictures Indoor units: Front Panel View Front Panel View Front Panel View Front Panel View Front Panel View Front Panel...
Page 11
View Front Panel View Front Panel View Front Panel View Front Panel View Outdoor Units:...
Page 12
Unit V(W1M) X(W1T) View F(W2M) D(W5F) Unit View B(W2T) Y(W1R) Unit View Remote controller: Model...
Model L5 (mm) (mm) (mm) (mm) (mm) (mm) (mm) AS-09UW4SVD**09A AS-09UW4SVD**9 AS-12UW4SVE**9 AS-09TR2SYD**01 AS-18UW4SXA** AS-18UW4SXA** AS-22UW4SBB** AS-22UW4SBB** AS-22TR2SBB**01 AS-24UR4SDB**9 365.5 AS-30UR4SDK**00 Note: “ ** ” mean code of Front Panel. 4. Installation Instruction To prevent abnormal heat generation and the possibility of fire, do not place obstacles, enclosures and grilles in front of or surrounding the air conditioner in a way that may clock air flow.
4-1. Installation Place and Condition Indoor unit Avoid: △ direct sunlight. △ nearby heat sources that may affect performance of the unit. △ areas where leakage of flammable gas may be expected. △ places where large amounts of oil mist exist. △...
Page 17
△ Choose a place as cool as possible. △ Choose a place that is well ventilated. △ Allow enough room around the unit for air intake or exhaust and possible maintenance. (see a1, b1 & c1) △ Provide a solid base (level concrete pad, concrete block, 10 × 40 cm beams or equal), a minimum of 10 cm above ground level to reduce humidity and protect the unit against possible water damage and decreased service life.
NOTE: In different models, the throttle assembly may be Capillary or Electronic expansion valve. 4-4. Air Purging and Leakage Test 1. Connect charging hose of manifold valve to charge end of low pressure valve (both high/low pressure valves must be tightly shut). 2.
6. Check the vacuum with the gage manifold valve, then close the gage manifold valve, and stop the vacuum pump. 7. Leave it for one or two minutes. Make sure the pointer of the gage manifold valve remains in the same position. 8.
Has the unit been connected to a secure It may cause electrical leakage. earth connection? It may cause electric malfunction or damage Is the power cord specified? the part. It may cause insufficient Are the inlet and outlet openings blocked? cooling(heating)capacity.
Mexico Glide Panel Model ; North America SEER 20 Model: Temperature Indoor Air Intake Temp. Outdoor Air Intake Temp Maximum 46 ℃ COOLING Minimum 16℃ -10℃ Maximum 30℃ 24℃ HEATING Minimum -10℃ Note: The parameters for generic only, the exact value please refer to the product specification.
Page 35
1.Major general technical parameters 1-1 Remote receiver distance(front of the air conditioner): 8 m. 1-2 Remote receiver angle: Less than 60 degrees. 1-3 Temperature control accuracy: ±1℃. 1-4 Time error: Less than 1%.、 2. Functions of the controller 2-1 Display panel I.
Page 36
(1)The Sleep mode can only be set during Cool, Heat and Dry mode. (2)When the appliance run in the Sleep mode, it will stop after 8 hours operation, then it will cancel the Sleep setting. When the appliance operate under the OFF-Timer setting condition, if the OFF-Timer setting less than 8 hours, it will keep the Sleep mode till the OFF-Timer setting;...
Page 37
When the difference between the setting temperature and the room temperature equal to 2℃ or 4℃, the indoor fan speed will keep in current speed. 3-6-3 Air flow direction control The louver is derived by a step motor, and it swings the horizontal louver automatically. Press the SWING button to swing or stop the louver.
Page 38
When the appliance turn in the anti-cold air system in the Extra-LOW (Tapped motor set in LOW, sic passim) during the compressor operation, the louver swing to the Cool air protection position, the louver recovers to the original position after the air volume change to LOW. When the room temperature reach to the setting temperature, the compressor will be turn off, and the air flow change to LOW, the louver swing to the Cool air protective position to prevent the air drop into human body directly;...
Page 39
Dehumidifying area I: Operation at the frequency in the range (30–60Hz) according to Dt (T indoor ambient-Test). Dt(℃) f(Hz) ≥2 Dehumidifying area II: The compressor stops for 5 minutes and operators for 5 minutes at the lowest frequency. Dehumidifying area III: The compressor stops. 3-10 Fan Only Mode Operation During the appliance run in this mode, the compressor and outdoor fan stop, the indoor fan operate under the pre-setting of air volume, and the louver swing, and the indoor fan speed same...
Page 40
Either of the above two conditions is met, the product will enter anti-freezing prohibition of frequency rising state. Anti-freezing prohibition of frequency rising operation: the compressor is kept at the current frequency, which may decrease according to situations while cannot rise. The outdoor fan runs. Condition for the end of anti-freezing prohibition of frequency rising state: when the temperature of indoor heat exchanger rises to “anti-freezing releasing temperature”, the state of anti-freezing prohibition of frequency rising is released.
Page 41
6. Electrical Characteristics 6-1. Print Circuit Board (Indoor & Outdoor) Model Print Circuit Board of Indoor unit Print Circuit Board of outdoor unit AS-09UW4SVD**9 AS-09UR4SVD**9 AS-12UW4SVE**9 1833235 1887379 AS-12UR4SVE**9 AS-12UW4SVE**09A AS-12UR4SVE**9 AS-18UW4SXA** 1833235 1841765 AS-18UR4SXA** AS-09TR2SYD**01易装 AS-12TE2SVE**03易装 AS-09TR2SYD**01 1550982 AS-12TR2SVE**03 AS-09UR4SVD**9 AS-18TR2SXA**01易装...
Page 42
1833235 Interface of PG motor Room temperature sensor Pipe temperature sensor Switch button Feedback from PG motor Up&down swing Left&right swing Wiring control or wifi interface Display interface Protective tube 1841766/1898224 Interface of PG motor Room temperature sensor Pipe temperature sensor Switch button Up&down swing Left&right swing...
Page 43
1550982 Interface of PG motor Room temperature sensor Pipe temperature sensor Switch button Feedback from PG motor Up&down swing Left&right swing Display interface Protective tube...
Page 44
1549681 Interface of PG motor Room temperature sensor Pipe temperature sensor Switch button Up&down swing Left&right swing Display interface Protective tube 1564090...
Page 49
Terminal of Terminal of neutral wire, Compressor 4-way valve compressor connect to the discharge terminal U/V/W phase terminal panel temperature sensor "1(N)" Terminal of live Terminal of Terminal of Terminal of wire, connect compressor electronic reactor to the terminal overload expansion valve panel "2(L)"...
Page 51
Terminal of Over Terminal of compressor Terminal of AC fan electronic pressure U/V/W phase( cool valve terminal expansion valve( sensor( RED/WHITE/BLUE) (WHITE) WHITE) WHITE) Outdoor ambient Terminal of reactor( Cool Valve temperature DRED BROWN/ORANGE)( terminal(WHITE) sensor(YELLOW Function Optional) Terminal of neutral wire, Outdoor pipe Heater connect to the terminal...
Page 52
Terminal of Terminal of Terminal of Terminal of DC compressor communication wire compressor W overload with filter board phase protector Compressor Terminal of discharge Terminal of live wire Terminal of electronic temperature with filter board compressor V phase expansion valve sensor Outdoor pipe 4-way valve...
Page 53
Outdoor ambient Terminal of temperature Terminal of AC fan Terminal of live wire compressor sensor Outdoor pipe Terminal of DC temperature Cool Valve terminal Terminal of neutral sensor Terminal of Heat Sink compressor temperature Heater terminal overload sensor protector Terminal of Pressure 4-way valve terminal electronic...
Page 54
Test in resistance. TOOL: Multimeter. Test the resistance of the main winding. The indoor fan motor is fault if the resistance of main winding 0(short circuit)or∞(open circuit). Test in voltage TOOL: Multimeter. Insert screwdriver into to rotate indoor fan motor slowly for 1 revolution or over, and measure voltage “YELLOW”...
Page 55
Outdoor DC Fan Motor 6-3. Temperature Sensor Parameter table attached: 1. THE PARAMETER OF THE INDOOR COIL AND INDOOR ROOM SENSOR ,THE PARAMETER OF THE OUTDOOR COIL AND OUTDOOR SENSOR: (R(0)=15k B(0/100)=3450) Temperature(℃ Temperature(℃ Resistance(k Resistance(k) Voltage(V) Voltage(V) 38.757 0.58143512 4.292 2.715076661 36.844...
Page 58
27.162 1.00111890 2.609 3.613561484 26.109 1.03315203 2.542 3.639477628 25.103 1.06573050 2.477 3.664977902 24.142 1.09883007 2.414 3.6900369 23.223 1.13246511 2.353 3.714629083 22.345 1.16658089 2.294 3.738728832 21.505 1.20120120 2.237 3.762310501 20.701 1.23631868 Note: the AD value in the table is calculated on the basis of the pull-down resistor is 6.8K. 6-4.
Page 59
Familiar error: 1)Sound abnormality 2)Insulation resistance disqualification. 6-6.Room Card Control, Fire Protection, ON/OFF Function 6-6-1.Instructions for the function setting of room card control, fire protection, ON/OFF function. 1. Factory setting ON/OFF function is tacitly approved to be invalid when out of factory while both the room card control and fire protection functions are valid.
Page 60
short circuit state under the factory state (an external short circuit plug shown as Figure 2). (Illustration: the socket number in circuit is subject to the actual serial number of PCB.) When using the room card control, the user cuts off the short wire shown in Figure 2 and connects the red lines to the control switch (supplied by user), and the connecting wire should be 22AWG or above specification.
Page 61
Exhibit 1: Built-in EE settings combination EE DATA Red Line (1+2) White Line (2+3) Void Void Hotel Room Card Control Void Void Fire Protection Control Hotel Room Card Control Fire Protection Control Void ON/OFF Reading and writing EE operations through wire remote controller are as follows: (1) Operations: In any state, hold down both “MODE”...
Page 62
In case of using or cancelling the room card control / fire protection / (ON/OFF) function, use the wire controller to modify the parameters of indoor unit. 2. Function introduction (1) Room card control: a kind of control mode to control the machine startup & shutdown based on the on & off state of the room card control port.
Page 63
Fig.5Hardware connection diagram 3.2 Timing sequence description: (1) Room card control: 1) Control of room card disconnection: the air conditioner shall be shut down after the room card control signal is disconnected. In this state, the indoor unit can’t be started. If the user performs starting operation, the wire controller shall not respond and displays power-off.
Page 64
6-7.Wiring Remote Controller Use And Installation Model Installation Manual Instructions YXE-C01U 1813253 1813254 YXE-D01U(E) 1898797 1898796 YXE-C02U(E) 1844538 1844539 YXE-A03U(E) Not available 1967341 Note: Installation Manual Installation Instructions separate documents. 7. Trouble Shooting 7-1. Error Code Table 1.Indication on the outdoor unit: When the unit has the following trouble and the compressor stops running, The LED of outdoor control board will show the error sequence automatically: NOTE: ★:LIGHT O:FLASH ×:OFF...
Page 65
a. the fan motor run abnormally; Current overload ★ × b. the condenser or and evaporator is dirty; protection c. the air inlet and outlet is abnormally a. the outdoor control board is short circuit; Maximum current b. the drive board is short circuit; ★...
Page 66
a. the connection of the outdoor fan motor is Outdoor fan loose; b. there are something block the motor locked ★ outdoor fan; c. the fan motor is rotor protection failure; d. the outdoor control board is failure a. the refrigerant is too much; Outdoor coil the outdoor fan motor is failure;...
Page 67
LED will show the other error code. Refer to the remote controller which the sleep key can set into 4 different combination ways (Hisense's new design remote controller), when using to check the error codes only takes effect for pressing the sleep key 10 times in ten seconds instead of 4 times.
Page 68
Remar The root cause is may be one Content of the following Normal a. The outdoor temperature The failure for sensor loose; temperature b. the outdoor temperature sensor of sensor is failure; outdoor coil c. The indoor control board is failure ×...
Page 69
× × Ο × a. the outdoor control board is short circuit; Maximum b. the drive board is short current circuit; protection c. the other components is short circuit × × Ο Communicatio ★ a. the connection wires connect n trouble loose between b.
Page 70
c. the outdoor control board is failure a. the connection of the outdoor × × Ο ★ fan motor is loose; Outdoor fan there are something block the motor locked outdoor fan; rotor protection the fan motor is failure; d. the outdoor control board is failure a.
Page 71
d. the connection between the filter board and the terminal is incorrect or loose; e. the indoor control board is failure; f. the PFC board is failure; g. the power board is failure; h. the outdoor control board is failure. Indoor a.
Page 72
b. the inner supply voltage of the unit is higher or lower than normal a. the communication cable ★ ★ connect loose; b. the communication cable is failure; c. the connection between the filter board and the outdoor control Communicatio board is incorrect or loose;...
Page 73
too high b. the refrigerant of the unit is not protection enough a. the indoor coil temperature Anti-freeze sensor connect loose; protection with b. the indoor coil temperature cooling or ★ ★ sensor is failure; overload c. the indoor control board is failure protection with d.
Page 74
f. The indoor control board is failure. d. The indoor coil temperature The failure for sensor loose; temperature e. The indoor coil temperature Ο Ο sensor of sensor is failure; indoor coil f. The indoor control board is temperature failure.
Page 75
There are two blue terminals on the outdoor control panel, as shown above. Application: Short out the terminals, and power up the outdoor unit, then the outdoor unit may run independently. It can be determined that there is no internal and external communication faults. When the environment temperature is lower than 18℃, you can't run the unit under the cool mode, but if you need run the unit at this moment ,such as add the gas or do more test, at this moment you can use this function,...
Page 76
value)Hz/S. The indoor and outdoor fans run. Conditions for ending over-current frequency decreasing: when the current drops below “current value for starting the refrigeration current protective prohibition of frequency rising (E2 value)”, over-current under-clocking will be released. 3.Prohibition of frequency increasing of compressor exhausting Conditions for prohibition of frequency rising of compressor discharge Condition 1: in the case of frequency decreasing of compressor discharge, the discharge temperature of the compressor drops below X4℃.
Page 77
7-5. Trouble Diagnosis of Electric Filter Board Visual examination: as the circuit is simple, the connection may be checked visually to see whether any loose or poor connection. Voltage test: the voltage at the input end shall be the same as the voltage at the output end. 7-6.