1. Safety Considerations IMPORTANT! Please Read Before Starting This air conditioning system meets strict safety and operating standards. As the installer or service person, it is animportant part of your job to install or service the system, so it operates safely and efficiently.
Page 5
firehazard. When Transporting Be careful when picking up and moving the indoor andoutdoor units. Get a partner to help, and bend yourknees when lifting to reduce strain on your back. Sharpedges or thin aluminum fins on the air conditioner cancut your fingers. When Installing ●In a Ceiling or Wall Make sure the ceiling/wall is strong enough to hold theunit’s weight.
Page 6
regulations 2. Marking of equipment using signs Compliance with local regulations 3. Disposal of equipment using flammable refrigerants Compliance with national regulations 4. Storage of equipment/appliances The storage of equipment should be in accordance with the manufacturer's instructions. 5. Storage of packed (unsold) equipment Storage package protection should be constructed such that mechanical damage to the equipment inside the package will not cause a leak of the refrigerant charge.
Page 7
Where electrical components are being changed, they shall be fit for the purpose and to the correct specification. At all times the manufacturer's maintenance and service guidelines shall be followed. If in doubt consult the manufacturer's technical department for assistance. The following checks shall be applied to installations using flammable refrigerants: –...
Page 8
8. Repair to intrinsically safe components Do not apply any permanent inductive or capacitance loads to the circuit without ensuring that this will not exceed the permissible voltage and current permitted for the equipment in use. Intrinsically safe components are the only types that can be worked on while live in the presence of a flammable atmosphere.
Page 9
This process may need to be repeated several times. Compressed air or oxygen shall not be used for this task. Flushing shall be achieved by breaking the vacuum in the system with OFN and continuing to fill until the working pressure is achieved, then venting to atmosphere, and finally pulling down to a vacuum.
Page 10
equipment are closed off. k) Recovered refrigerant shall not be charged into another refrigeration system unless it has been cleaned and checked. 15.Labelling Equipment shall be labelled stating that it has been de-commissioned and emptied of refrigerant. The label shall be dated and signed. Ensure that there are labels on the equipment stating the equipment contains flammable refrigerant.
Page 11
The appliance shall be stored in a well-ventilated area where the room size corresponds to the room area as specified for operation. The appliance shall be stored in a room without continuously operating open flames (for example an operating gas appliance) and ignition sources (for example an operating electric heater). Any person who is involved with working on or breaking into a refrigerant circuit should hold a current valid certificate from an industry-accredited assessment authority, which authorized their competence to handle refrigerants safely in accordance with an industry recognized assessment...
2. Product Specifications Note: “**” mean code of Front Panel(See in 3-1 .Product Pictures). AS-09UR4RMEDJ00 AS-12TR4RMEDJ01 Model No. AS-09TR4RMEDJ00 T1, C INVERTER T1, H, INVERTER T1, C, INVERTER Type Ratings 2500 2500 3500 Cooling Capacity 3200 Heating Capacity Rated Input-Cooling...
Page 13
Range Cooling Operating -15-50 -10-50 Temperature Range ℃ Heating Operating Temperature Range ℃ -10-24 Features Hidden display LCD Wireless Remote Controller Removable and washable Panel Washable PP Filter Silver Ion filter 24 Hours Timer 5 Speed and Auto Indoor Fan Control Vertical Auto Swing Louver Horizontal Auto Swing Louver Dimmer...
Page 14
AS-12UR4RXEDJ00 AS-24TR4RBBDJ01 AS-24UR4RBBDJ01 Model No. T1, C INVERTER T1, H, INVERTER T1, H, INVERTER Type Ratings 3500 Cooling Capacity 7100 7100 Heating Capacity 4000 8000 Rated Input-Cooling 1975 1975 Rated Input-Heating 2250 Moisture Removal High m3/h 1150 1150 Air Circulation Mid m3/h Low m3/h 4.35...
Page 15
Heating Operating -10-24 -10-24 Temperature Range ℃ Features Hidden display LCD Wireless Remote Controller Removable and washable Panel Washable PP Filter Silver Ion filter 24 Hours Timer 5 Speed and Auto Indoor Fan Control Vertical Auto Swing Louver Horizontal Auto Swing Louver Dimmer Sleep Operation Smart Function...
Remote controller: Model View 3-2. Product dimensions Indoor units:...
Page 18
Model W (mm) H (mm) D (mm) AS-09TR4RMEDJ00 AS-09UR4RMEDJ00 AS-12TR4RMEDJ01 AS-12UR4RXEDJ00 AS-24TR4RBBDJ01 1087 AS-24UR4RBBDJ01 Outdoor units: Model (mm) (mm) (mm) (mm) (mm) (mm) (mm) AS-09TR4RME**00 AS-09UR4RME**00 AS-12TR4RME**01 AS-12UR4RXE**00 AS-24TR4RBB**01 AS-24UR4RBB**01 Note: “**” mean code of Front Panel.
4. Installation Instruction To prevent abnormal heat generation and the possibility of fire, do not place obstacles, enclosures and grilles in front of or surrounding the air conditioner in a way that may clock air flow. And, more than 1 meter away from anyantenna or powerlines or connecting wires used for TV, radio, telephone, security system, or intercom.
Page 20
5/8"(Ø15.88) 3/8"(Ø9.52) 3/8"(Ø9.52) * If total tubing length becomes 7.5 to 15 m (max.), charg becomes 7.5 to 15 m (max.), charge additional refrigerant e additional refrigerant as the table1 for reference.And no additional compressor oil is necessary o additional compressor oil is necessary. Outdoor unit Avoid: △Heat sources, exhaust fans, etc.
Page 21
Recommended Wire Diameter: Capacity size Wire Diameter(mm Fuse or Circuit Breaker Capacity 5K~12k 1.0(Power wire)/1.0(Connect wire) 3.15A or 5A(indoor)/15A(outdoor) 2.5(Power wire)/1.5(Connect wire) 3.15A or 5A(indoor)/20A(outdoor) 22K~30K 2.5(Power wire)/2.5(Connect wire) 3.15A or 5A(indoor)/30A(outdoor)...
4-2. Electric Wiring Diagram Model Indoor Unit DIAGRAM Outdoor Unit DIAGRAM 1957918 1957918 AS-09TR4RMEDJ00 1957918 1957918 AS-09UR4RMEDJ00 1957918 1957918 AS-12TR4RMEDJ01 1957918 1957918 AS-12UR4RXEDJ00 1957918 1957918 AS-24TR4RBBDJ01 1957918 1957918 AS-24UR4RBBDJ01 Note: “**” mean code of Front Panel. Indoor Unit DIAGRAM: 1957918...
4-4. Air Purging and Leakage Test 1. Connect charging hose of manifold valve to charge end of low pressurevalve (both high/low pressure valves must be tightly shut). 2. Connect joint of charging hose to vacuum pump. 3. Fully open the handle of Lo manifold valve. 4.
4-5. Test Running △Check after Installation Items to be checked Possible malfunction Has it been fixed firmly? The unit may drop, shake or emit noise. It may cause insufficient Have you done the refrigerant leakage test? cooling(heating)capacity Is heat insulation sufficient? It may cause condensation and dripping.
5. Function Operation 5-1. Operation Range (cooling and heating) Temperature Indoor Air Intake Temp. Outdoor Air Intake Temp 50℃ Maximum COOLING Minimum 16℃ -15℃ Maximum 30℃ 24℃ HEATING Minimum -10℃ Note: The parameters for generic only, the exact value please refer to the product specification.
5-2. Remote Controller Operation & Function Remote ControllerInstruction △ R2-01...
Page 29
FunctionInstruction △ 1.Major general technical parameters 1-1 Remote receiver distance(front of the air conditioner): 8 m. 1-2 Remote receiver angle: Less than 60 degrees. 1-3 Temperature control accuracy: ±1℃. 1-4 Time error: Less than 1%. 2. Functions of the controller 2-1 Display panel I.
Page 30
3-3 Timer function Real time of Timer setting (1) The max Timer ranges is 24 hours. (2) Timer ON/OFF (3) Timer ON/OFF can be set available in turn. (4) The Timer accurate more than 97% (5) The Timer can be adjusted by 1 min increase. (6) The appliance can be set the ON-Timer and OFF-Timer in the same time, but no any timer setting indicated.
Page 31
volume is set to LOW and the fan speed can be adjusted After the appliance start the smart operation, the setting temperature can be adjusted 2℃ or 7℃ (based on the remote mode)(the min accuracy is 1℃) up and down base on the automatic temperature setting, also the presetting temperature of PCB circuit.
Page 32
When the heating is changed to the cooling, it needs an interval of 50 seconds for the 4-way valve to change over from being activated to being interrupted. 3-7 Heating-run mode 3-7-1 Temperature compensation The temperature compensation is 5º in heating mode. For example, if the set temperature is 25℃ by the remote control, when the room temperature is detected with 31℃, the compressor will turn off.
Page 33
When the difference between the setting temperature and the room temperature equal to 2℃ or 4℃, the indoor fan speed will keep in current speed. 3-7-3Air flow direction control The horizontal louver is controlled by a step motor, press the SWING button to swing or stop the louver.
Page 34
Dehumidifying area I: Operation at the frequency in the range (30–60Hz) according to Dt (T indoor ambient-Test). Dt(℃) f(Hz) ≥2 Dehumidifying area II: The compressor stops for 5 minutes and operators for 5 minutes at the lowest frequency. Dehumidifying area III: The compressor stops. 3-10 Fan Only Mode Operation During the appliance run in this mode, the compressor and outdoor fan stop, the indoor fan operate under the pre-setting of air volume, and the louver swing, and the indoor fan speed same as...
5-3. Special Function Instruction Conditions of anti-freezingprohibition of frequency rising: Condition 1: in the case of anti-freezingfrequency decreasing, the temperature of indoor heat exchanger rises to “anti-freezing frequency decreasing temperature”. Condition 2: in normal operation, the temperature of indoor heat exchanger reaches “anti-freezing prohibition of frequency rising temperature”.
6-2. Fan Motor Drawings attached: DG13G1-16、DG13G2-07 Test in resistance. TOOL: Multimeter. Test the resistance of the main winding. The indoor fan motor is fault if the resistance of main winding 0(short circuit)or∞(open circuit). Test in voltage TOOL: Multimeter. Insert screwdriver into to rotate indoor fan motor slowly for 1 revolution or over, and measure voltage “YELLOW”...
Page 41
Indoor DC Fan Motor Outdoor DC Fan Motor...
6-4. Compressor Drawings attached: OVERLOAD PROTECTION INVERTER POWER & CONTROLLER Test in resistance. TOOL: Multimeter. Test the resistance of the winding. The compressor is fault if the resistance of winding 0(short circuit)or∞(open circuit) Familiar trouble: 1)Compressor motor lock. 2)Discharge pressure value approaches static pressure value .3)Compressor motor winding abnormality.
7.Trouble Shooting 7-1. Error Code Table 1.Indication on the outdoor unit: When the unit has the following trouble and the compressor stops running, The LED of outdoor control board will show the error sequence automatically: NOTE: ★: LIGHT : FLASH :...
Page 47
a. he EEPROM chip is loose; Outdoor b. the EEPROM chip inserted with opposite EEPROM in ★ ★ ★ direction; trouble c. the EEPROM chip is failure Compressor a. the compressor exhaust temperature sensor is exhaust failure; ★ temperature too b.
Page 48
a. The IPM board is failure; b. The outdoor fan is broken; c. The outdoor fan motor is failure; IPM module d. The outdoor fan has been blocked ; protection e. The condenser is dirty; f. The outdoor unit has been installed without standard.
Page 49
LED will show the other error code. 2.2.2 Refer to the remote controller which the sleep key can set into 4 different combination ways (Hisense's new design remote controller), when using to check the error codes only takes effect for pressing the sleep key 10 times in ten seconds instead of 4 times.
Page 50
Runnin Time Slee Erro Remark:★Light o Flash x OFF Remar The root cause is may be one of the Content following Normal The failure a. The outdoor temperature sensor loose; temperature b. the outdoor temperature sensor is sensor of failure; outdoor coil c.The indoor control board is failure ...
Page 51
a.the outdoor control board is short Maximum circuit; current b.the drive board is short circuit; protection c.the other components is short circuit ★ Communicati on trouble a. the connection wires connect loose between b.
Page 52
Compressor a. the outdoor drive board is failure; drive in b. the compressor is failure trouble c. the outdoor control board is failure ★ a. the connection of the outdoor fan Outdoor fan motor is loose;...
Page 53
board and the terminal is incorrect or loose; e. the indoor control board is failure; f.the PFC board is failure; g.the power board is failure; h. the outdoor control board is failure. Indoor a. The EEPROM chip loose; EEPROM ★ ★...
7-2. Test the jumper terminals Note: When the whole machine is powered up, if the external unit does not work, to rule out the communications failures, adopt screening method such as short circuit on the jumper terminals to see if the external unit can be started normally or similar method.
Page 55
compressor and outdoor fan stop, but indoor fan runs normally. Condition for ending over-current protection: when the current drops below “current value for releasing the refrigeration current protection (E2 value)”, over-current protection will be released. 2.Frequency decreasing for over-current Conditions for over-current frequency decreasing: if the current is equal to or greater than “current value for starting the refrigeration current protective frequency decreasing (E2 value)”, over-current frequency decreasing starts.
7-4. Trouble Diagnosis of Compressor Judging the connecting terminals of inverter compressor: It is impossible to identify terminals U, V and W of inverter compressor with multi-meter. Just connect the terminals in the same way as the original unit when replacing the compressor. A wrong connection will lead to reverse and loud noise of the compressor.
Page 62
AC voltage test point: Sensor test point:...
Page 63
test point: Check the screw of IPM fastening:...
Page 64
test point: Forward of IPM P-U/P-V/P-W test : Reverse of IPM P-U/P-V/P-W test: Forward of IPM N-U/N-V/N-W test : Reverse of IPM N-U/N-V/N-W test :...
Page 65
test point: The resistance of the compressor U-W\V-W SI and N test point:...