9. WIRING DIAGRAM
● Pay attention to the following items while the system is running.
Do not touch any of the parts by hand at the discharge gas side, since the compressor chamber
and the pipes at the discharge side are heated higher than 90℃.
Note:
Follow local codes and regulations when select field wires, and all the above are the minimum
(1)
wire size.
Use the wires which are not lighter than the ordinary polychloroprene sheathed flexible cord.
(2)
(Cord designation H07RN-F).
The wire sizes marked with *1 in the above table are selected at the maximum current of the
(3)
unit according to the National Standard, EN60335-1.
When transmitting cable length is more than 15 meters, a larger wire size should be selected.
(4)
Install main switch and ELB for each system separately. Select the high response type ELB that
(5)
is acted within 0.1second. Recommended capacity to see table above.
In the case that power cables are connected in series, add each unit maximum current and
(6)
select wires below.
Selection According to EN60335-1
Current i(A)
i≤6
6<i≤10
10<i≤16
16<i≤25
25<i≤32
32<i≤40
40<i≤63
63<i
*In the case that current exceeds 63A, do not connect cables in series.
2
Wire Size (mm
)
0.75
1
1.5
2.5
4
6
10
*
83