M-system R7ML-DC16B Instruction Manual

Pnp transistor output module, 16 points (mechatrolink-i / -ii)
Hide thumbs Also See for R7ML-DC16B:

Advertisement

Quick Links

INSTRUCTION MANUAL
PNP TRANSISTOR OUTPUT MODULE, 16 points
(MECHATROLINK-I / -II)
BEFORE USE ....
Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System's Sales Office or representatives.
■ PACKAGE INCLUDES:
Discrete output module .............................................. (1)
■ MODEL NO.
Confirm that the model number described on the product is
exactly what you ordered.
■ INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
POINTS OF CAUTION
■ CONFORMITY WITH EU DIRECTIVE
• Use MECHATROLINK-II network cable with core (Yasu-
kawa Controls Model JEPEC-W6003-x-E) or equivalent
for the network.
• Be sure to earth FG terminal.
• The actual installation environments such as panel con-
figurations, connected devices and connected wires may
affect the protection level of this unit when it is integrat-
ed in a panel system. The user may have to review the CE
requirements in regard to the whole system and employ
additional protective measures to ensure CE conformity.
■ POWER INPUT RATING & OPERATIONAL RANGE
• Locate the power input rating marked on the product and
confirm its operational range as indicated below:
24V DC rating: 24V ±10%, approx. 85mA
■ GENERAL PRECAUTIONS
• Before you remove the unit or mount it, turn off the power
supply and input signal for safety.
■ ENVIRONMENT
• Indoor use.
• When heavy dust or metal particles are present in the
air, install the unit inside proper housing with sufficient
ventilation.
• Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within 0 to 55°C (32
to 131°F) with relative humidity within 30 to 90% RH in
order to ensure adequate life span and operation.
■ WIRING
• Do not install cables close to noise sources (relay drive
cable, high frequency line, etc.).
• Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
• FG terminal is NOT a protective conductor terminal.
■ AND ....
• The unit is designed to function as soon as power is sup-
plied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data
sheet.
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
R7ML-DC16B
R7ML-DC16B
MODEL
EM-7805-H Rev.2
P. 1 / 10

Advertisement

loading

Summary of Contents for M-system R7ML-DC16B

  • Page 1 BEFORE USE ..POINTS OF CAUTION ■ CONFORMITY WITH EU DIRECTIVE Thank you for choosing M-System. Before use, please check contents of the package you received as outlined below. • Use MECHATROLINK-II network cable with core (Yasu- If you have any problems or questions with the product, kawa Controls Model JEPEC-W6003-x-E) or equivalent please contact M-System’s Sales Office or representatives.
  • Page 2: Component Identification

    STATION ADD. B. RATE 10 11 12 13 15 16 17 18 Power Supply Terminals Output Terminals ■ LEFT SIDE VIEW MECHATROLINK Connector EM-7805-H Rev.2 P. 2 / 10 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...
  • Page 3 (maintains the last data received normally) Caution ! - SW1-3, 1-5, 1-6, 1-7, 1-8 are unused. Be sure to turn off unused ones. EM-7805-H Rev.2 P. 3 / 10 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...
  • Page 4: External Dimensions

    ■ Output Connection Example – +24V 24V DC *MECHATROLINK connectors are internally connected. The network cable can be connected to either one. EM-7805-H Rev.2 P. 4 / 10 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...
  • Page 5: Wiring Instructions

    Transmission cycle: 0.5 msec., 1 msec., 1.5 msec., 2 msec., 4 msec., 8 msec. Data length: 17 bytes / 32 bytes selectable (Must choose identical data size for all stations on one network) EM-7805-H Rev.2 P. 5 / 10 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...
  • Page 6 Byte 17 through 31 depend upon the Application Layer Command type. These bytes are unavailable for MECHATROLINK-I, or MECHATROLINK- II in the 17- byte mode. EM-7805-H Rev.2 P. 6 / 10 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...
  • Page 7 Byte 17 through 31 are always 0 in the 32-byte mode. These bytes are unavailable for MECHATROLINK-I, or MECHATROLINK-II in the 17- byte mode. EM-7805-H Rev.2 P. 7 / 10 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...
  • Page 8 Byte 17 through 31 are always 0 in the 32-byte mode. These bytes are unavailable for MECHATROLINK-I, or MECHATROLINK-II in the 17-byte mode. EM-7805-H Rev.2 P. 8 / 10 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...
  • Page 9 CH4 data, low 8 bits R7ML-DA16, R7ML-DC16x, R7ML-YS2, R7ML-YV2 : Unused CH4 IN HI CH4 data, high 8 bits R7ML-DA16, R7ML-DC16x, R7ML-YS2, R7ML-YV2 : Unused EM-7805-H Rev.2 P. 9 / 10 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...
  • Page 10 Status data to be sent from the slave to the master are set in the response. Refer to “I/O DATA DESCRIPTIONS.” I/O DATA DESCRIPTION DISCRETE OUTPUT Output 0 Output 1 Output 2 Output 3 Output 7 Output 8 Output 15 0:OFF 1:ON EM-7805-H Rev.2 P. 10 / 10 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...