M-system R7M-DAC16C Instruction Manual

Npn discrete input & npn transistor output module, 8 points each (modbus 115.2 kbps)

Advertisement

Quick Links

INSTRUCTION MANUAL
NPN DISCRETE INPUT & NPN TRANSISTOR OUTPUT
MODULE, 8 points each
BEFORE USE ....
Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System's Sales Office or representatives.
■ PACKAGE INCLUDES:
Discrete I/O module ............................................................(1)
■ MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
■ INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
(Modbus 115.2 kbps)
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
MODEL
POINTS OF CAUTION
■ CONFORMITY WITH EU DIRECTIVES
• The equipment must be mounted inside the instrument
panel of a metal enclosure.
• The actual installation environments such as panel con-
figurations, connected devices, connected wires, may af-
fect the protection level of this unit when it is integrated
in a panel system. The user may have to review the CE
requirements in regard to the whole system and employ
additional protective measures to ensure the CE conform-
ity.
• Install lightning surge protectors for those wires connect-
ed to remote locations.
■ POWER INPUT RATING & OPERATIONAL RANGE
• Locate the power input rating marked on the product and
confirm its operational range as indicated below:
24V DC rating: 24V ±10%, approx. 40mA
■ GENERAL PRECAUTIONS
• Before you remove the unit or mount it, turn off the power
supply, input and output signal for safety.
• Before you remove the terminal block or mount it, turn
off the power supply, input and output signal for safety.
• DO NOT set the switches on the module while the power
is supplied. The switches are used only for maintenance
without the power.
■ ENVIRONMENT
• Indoor use.
• When heavy dust or metal particles are present in the
air, install the unit inside proper housing with sufficient
ventilation.
• Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -10 to +55°C
(14 to 131°F) with relative humidity within 30 to 90% RH
in order to ensure adequate life span and operation.
• Be sure to close the terminal cover for safety.
■ WIRING
• Do not install cables close to noise sources (relay drive
cable, high frequency line, etc.).
• Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
■ AND ....
• The unit is designed to function as soon as power is sup-
plied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data
sheet
R7M-DAC16C
EM-7803-AK Rev.4 P. 1 / 8

Advertisement

loading

Summary of Contents for M-system R7M-DAC16C

  • Page 1 (Modbus 115.2 kbps) BEFORE USE ..POINTS OF CAUTION Thank you for choosing M-System. Before use, please check ■ CONFORMITY WITH EU DIRECTIVES contents of the package you received as outlined below. • The equipment must be mounted inside the instrument If you have any problems or questions with the product, panel of a metal enclosure.
  • Page 2: Component Identification

    • Output ON Time (SW1-6, 1-7, 1-8) SW1-6 SW1-7 SW1-8 OUTPUT ON TIME 100 ms (*) 200 ms 300 ms 500 ms 10 s EM-7803-AK Rev.4 P. 2 / 8 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...
  • Page 3 NONE / ODD / EVEN NONE ■ CHANNEL INDIVIDUAL SETTING PARAMETER AVAILABLE RANGE DEFAULT SETTING Output Operation Mode Maintained / Momentary ---- EM-7803-AK Rev.4 P. 3 / 8 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...
  • Page 4: Terminal Connections

    Note: In order to improve EMC performance, bond the FG terminal to ground. Caution: FG terminal is NOT a protective conductor terminal. I/O Connection Examples C– – C– 24V DC EM-7803-AK Rev.4 P. 4 / 8 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...
  • Page 5: Communication Cable Connections

    Note: If Bit 0 receives multiple data during the one-shot output time period, the Y0 provides only the last output data received within approx. 25 milliseconds after the period. EM-7803-AK Rev.4 P. 5 / 8 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...
  • Page 6 Unused ---- ---- Unused ---- ---- Unused ---- ---- Unused ---- ---- Unused ---- ---- Unused ---- ---- Unused ---- ---- Unused EM-7803-AK Rev.4 P. 6 / 8 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...
  • Page 7 I: Integer, -1500 – +11500 (-15 – +115%) F: Floating Note: DO NOT access addresses other than mentioned above. Such access may cause problems such as inadequate operation. EM-7803-AK Rev.4 P. 7 / 8 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...
  • Page 8: Wiring Instructions

    Applicable wire size: 0.25 to 1.65 mm (AWG 22 to 16) Recommended manufacturer: Japan Solderless Terminal MFG. Co., Ltd, Nichifu Co., Ltd 3.3 (.13) max mm (inch) EM-7803-AK Rev.4 P. 8 / 8 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...