System Pressures
Technicians with R-22 experience will need to become familiar working with high and low
side pressures that are much higher when using R-410A. A typical R-22 system operates
normally with a high side pressure of approximately 260 psi @ 120°F condensing
temperature and a low side pressure of approximately76 psi @ 45°F evaporator
saturation temperature.
A normally operating R-410A system with the same condensing temperature of 120°F and
45°F evaporator saturation temperature will have a high side pressure of approximately
500 psi and a low side pressure of approximately 150 psi.
5/16" socket or drive
1/4" socket or drive – Ground screws and control assembly use 1/4" machine thread screws
3/8" socket or drive – For outdoor fan blade removal
4 mm Allen wrench – For indoor fan blade removal
Volt Ohm Meter
Amp probe
Needlepoint meter leads
Sealed system and R-410A recovery equipment
Thermal paste (Part #: WX5X8927)
Extension needed for condenser shroud screws
Additional Safety Requirements

Tools Required