Fan Cycle - Resistance Heating Mode
The indoor fan and heaters are turned On at the same time. The indoor fan is turned O , approximately 20
seconds after the heaters are de-energized as shown. In the o mode, the indoor fan will continue to operate
for six seconds after the user has stopped the Zoneline, in order to dissipate the heat inside the Zoneline.
In the heating mode, the indoor fan is designed to operate at two di erent speeds (RPM).
FAN CYCLE - RESISTANCE HEATING MODE
Temperature
Temperature Setting
-1.8°F
Heater
ON
ON
INDOOR FAN
ON
20 sec
– 15 –