◎Safety protection level of this unit is class I. The grounding wire should be firmly fixed at the "FG" terminal ( ) of the rack. The total leakage current of the rack system (including 3 * RCP-1000 units and 1 RCP-1U rack) is less than 3.5mA.
◎ Rack system MODEL RCP-3K1U□-12 RCP-3K1U□-24 RCP-3K1U□-48 RECTIFIER RCP-1000-12 RCP-1000-24 RCP-1000-48 RACK SHELF RCP-1UI or RCP-1UT OUTPUT VOLTAGE OUTPUT MAX. OUTPUT CURRENT 180A 120A MAX. OUTPUT POWER 2160W 2880W 3024W Note.5 VOLTAGE RANGE 90 ~ 264VAC 127 ~ 370VDC Note.4...
3.5.1 Adjustment of single unit Output voltage of one RCP-1000 is adjustable through the potentiometer (SVR51, can be found under the small circular hole on top of the unit). Please use a cross-screwdriver with isolated holder to make the adjustment.
Page 8
The resistors R1, R2 mentioned in Figure 3-1 should be added independently and the minimum wattage rating is 0.1W. Please refer to 3.5.4~3.5.6 about the selection of resistance. 3.5.4 Reference resistance value of R1/R2 for RCP-1000-12 Vout (%) Vout (%) R1 (Ω)
Over Temperature Alarm ◎ Every RCP-1000 single unit has a detecting circuit to sense its internal temperature. The value of internal temperature can ℃± ℃ only be read through the I C interface: when the internal temperature of RCP-1000 is higher than 60 3 , there will be an alarm signal sent out through the I C interface.
Figure 3-6: Location of the "clip" on RCP-1000 unit 3.17 Parallel Operation 3.17.1 Operation of single rack ◎ Internal parallel operation in single rack is only suitable for using the same RCP-1000 unit (single unit with the same output voltage and current). ◎ □...
◎ Higher output voltage can be acquired by connecting different racks in series. ◎ The racks □ connected in series should have the same single unit (RCP-1000-□) in each rack. Please refer to (RCP-1U ) Figure 3-8 for the reference connection method.
Page 12
In addition, each RCP-1000 unit should have its unique device address to communicate over the bus. The address can be assigned by the 9-pole DIP switch on the rack. In one RCP-1U rack, there are a total of 3 RCP-1000 units, and each RCP-1000 has a 3-pole addressing switch (refer to the following diagram).
Page 13
(1)The DIP switch is used for the bus device addressing configuration. Poles 1 to 3 are for setting the address of the A module, poles 4 to 6 are for the B module, and poles 7 to 9 are for the C module. Module DIP switch position...
Page 14
Temperature 0~100℃ 0.391 /bit For example, if the temperature reading value of RCP-1000-24 is "0x52", then convert to decimal value will be "82". 82(value) x 0.391(resolution for 24V temperature) = 32.062℃ 3.Reading example Read output current data of Output & Temperature from the RCP-1000-48 unit with address "0".
Page 15
The following example will explain how to read the Operational Status and output voltage of Output & Temperature from a RCP-1000-48C. 1.Set the address of the RCP-1000-48C to "0". If installed in the far right slot of a RCP-1U , set poles 1-3 of the 9-pole DIP switch (ADDRESS SWITCH) to the ON/ON/ON positions.
◎ This is a power supply with built-in DC fan and please make sure that the ventilation is not blocked. It is suggested that there should be no barriers within 10cm of the ventilating holes. ◎ Connect AC source to the AC input for A, B, C module position respectively depending on the RCP-1000 units assembled into □ the RCP-1U rack.
Warranty ◎Three years of global warranty is provided for RCP series under normal operation. Please do not change any component or modify the unit by yourself or MEAN WELL may reserve the right not to provide the complete warranty service.
Page 18
N o . 2 8 , W u q u a n 3 r d R d . , W u g u D i s t . , N e w Ta i p e i C i t y 2 4 8 , Ta i w a n...
Need help?
Do you have a question about the RCP-1000 and is the answer not in the manual?
Questions and answers