Über die gesetzliche Gewährleistung hinausgehende Garantieangaben sind Herstellergarantien.
1000W Single Output Power Supply
SPECIFICATION
MODEL
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
RIPPLE & NOISE (max.)
OUTPUT
VOLTAGE ADJ. RANGE
VOLTAGE TOLERANCE
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE
FREQUENCY RANGE
POWER FACTOR (Typ.)
INPU T
EFFICIENCY (Typ.)
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
LE AKAGE CURRENT
OVERLOAD
PROTECTION
OVER VOLTAGE
OVER TEMPERATURE
AUXILIARY POWER(AUX)
REMOTE ON/OFF CONTROL
FUNCTION
DC OK SIGNAL
OUTPUT VOLTAGE TRIM
CURRENT SHARING(CS)
WORKING TEMP.
WORKING HUMIDITY
ENVIRONMENT
STORAGE TEMP., HUMIDITY
TE MP. COEFFICIENT
VIBRATION
SAFETY STANDARDS
WITHSTAND VOLTAGE
SAFE TY &
ISOLATION RESISTANCE
EMC
(Note 4)
EMC EMISSION
EMC IMMUNITY
MTBF
OTHERS
DIMENSION
PACKING
NOTE
RSP-1000-12
RSP-1000-15
12V
15V
60A
50A
0 ~ 60A
0 ~ 50A
720W
750W
150mVp-p
150mVp-p
Note.2
10 ~ 13.5V
13.5 ~ 16.5V
±1.0%
±1.0%
Note.3
±0.5%
±0.5%
±0.5%
±0.5%
300ms, 50ms at full load
16ms/230VAC
16ms/115VAC at full load
90 ~ 264VAC
127 ~ 370VDC
Note.5
47 ~ 63Hz
0.95/230VAC
0.98/115VAC at full load
83%
85%
12A/115VAC
6A/230VAC
25A/115VAC
40A/230VAC
<2.0mA / 240VAC
105 ~ 125% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed
13.8 ~ 16.8V
17 ~ 20.5V
Protection type : Shut down o/p voltage, re -power on to recover
℃± ℃
85
5
(TSW2 ) detect on heatsink of O/P diode; 7
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
5V @ 0.5A (+5%, -8%)
Power on : short between on/off(pin6) & -S (pin2) on CN50
Note.6
The TTL signal out, PSU turn on = 0 ~ 1V ; PSU turn off = 3.3 ~ 5.6V
Adjustment of output voltage is possible between 40 ~ 110% of rated output
Note.6
Please refer to function manual
Note.7
-20 ~ +60℃ (Refer to "Derating Curve")
20 ~ 90% RH non-condensing
℃
-40 ~ +85 , 10 ~ 95% RH
±
℃
℃
0.02%/
(0 ~ 50
)
10 ~ 500H z, 2G 10min./1cycle, 60min. eac h along X, Y, Z axes
UL60950-1, TUV EN60950-1 approved
I/P-O/P:3KVAC
I/P-FG:2KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH
Compliance to EN55022 (CISPR22), EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2, EN61204-3, heavy industry level, criteria A
116.75K hrs min.
MIL-HDBK -217F (25 )
295*127*41mm (L*W*H)
1.95Kg; 6pcs/12.7Kg/1.15CUFT
■
‧
‧
‧
‧
‧
‧
‧
‧
‧
‧
‧
‧
‧
‧
RSP-1000-24
24V
40A
0 ~ 40A
960W
150mVp-p
20 ~ 26.4V
±1.0%
±0.5%
±0.5%
88%
27.6 ~ 32.4V
℃± ℃
5
5
(TSW1 ) detect on heatsink of power transistor
Power off : open between on/off(pin6) & -S (pin2) on CN50
O/P-F G:0.5KVAC
℃
℃
℃
R S P - 1 0 0 0
RSP-1000-27
RSP-1000-48
27V
48V
37A
21A
0 ~ 37A
0 ~ 21A
999W
1008W
150mVp-p
150mVp-p
24 ~ 30V
43 ~ 55V
±1.0%
±1.0%
±0.5%
±0.5%
±0.5%
±0.5%
88%
90%
31 ~ 36.5V
56.6 ~ 66.2V
File Name:RSP-1000-SPEC 2013-09-03
s e r ie s
Need help?
Do you have a question about the RSP-1000 Series and is the answer not in the manual?
Questions and answers