3. System remote controller
Environment specification
Item
Connected Equipment
Number of Units
Neuron CHIP
Network Transceiver
Average communication capacity
Performance
Peak communication capacity
The proper communication is not obtainable when communication intervals exceed its performance, assure sufficient intervals.
ACK Service is recommended for the network service.
Detailed specifications for the L
" FT3120/FT3150 Smart Transceiver Data Book " by Echelon Corporation.
<LMAP02-E Network Variables>
Request On/Off
Request Mode
Setpoint from network
(set temp.)
Request Fanspeed
Request prohibit
(note4)
local On/Off
Request prohibit
(note4)
local Mode
Request prohibit
(note4)
local Setpoint
(note1) The case of CITY MULTI is indicated.
(note2) There is a case which cannot be used with the system configuration of the air conditioners units.
(note3) "n" of the network variable shows indoor unit address (M-NET).
(note4) It is possible to use when the "MA/ME" remote controller.
External dimension
59.6 [
2-
3
/
]
8
A
9.6 [
]
3
/
8
MITSUBISHI ELECTRIC
( For details of the connectable models,please contact the dealer.)
LMAP can control 50 indoor units (including LOSSNAY)
TMPN3150/FT3150-P20 (10MHz)
FTT-10A/FT-X1 (Free Topology 78kbps)
2.5 inputs/second
50 inputs/second (for one second)
W
®
network can be found in " FTT-10A Free Topology Transceiver User's Guide " or
ON
ORKS
Network Variables
nviOnOff_n
nv1n
nviMode_n
nv3n
nv5n
nviSetPoint_n
nv7n
nviFanSpeed_n
nv19n
nviProOnOff_n
nv21n
nviProMode_n
nviProSetPoint_n
nv23n
360 [
14-
3
/
]
16
240 [
9-
1
/
]
60 [
2-
3
/
]
2
8
CONTROLLER
Description
Multiple split-type air conditioners
Split-type air conditioners
Heat recovery ventilators
nvoOnOff_n
nv2n
On/Off state
nvoMode_n
nv4n
Mode state
Setpoint state
nv6n
nvoSetPoint_n
(set temp.)
nv8n
nvoFanSpeed_n
FanSpeed state
nv10n
nvoThermo_n
Thermo On/Off state
Indoor Temperature state
nv12n
nvoSpaceTemp_n
nvoAlarm_n
nv16n
Alarm signal
Prohibit local
nvoProOnOff_n
nv20n
On/Off state
Prohibit local
nv22n
nviProMode_n
Mode state
Prohibit local
nv24n
nviProSetPoint_n
Setpoint state
Item
Dimensions
Net Weight
Power Source
Current Consumption
Operating Range
Temperature
Operation
Storage Range
Environment
Humidity
Installation Environment
Detail of A section
4.5 [
]
3
/
16
C7-R Rev.
CITY MULTI
Mr.Slim
LOSSNAY
(note4)
(note4)
(note4)
Unit:mm[in.]
Description
340 (H) x 360 (W) x 59.6 (D)
7
3
3
[13-
/
(H) x 14-
/
(W) x 2-
/
(D)]
16
16
8
3.3 kg
~ 220 - 240V (50/60 Hz)
50 mA (Maximum)
30 to 95 RH (No condensation)
Inside the metal control board (indoor)
3 - 26