Mitsubishi Electric CITY MULTI PEFY-P22VMS-E-S Data Book page 318

Table of Contents

Advertisement

2. M-NET control
2-1. Transmission cable length limitation
2. M-NET control
2-1-1. Using MA Remote controller
Long transmission cable causes voltage down, therefore, the length limitation should be obeyed to secure proper transmission.
Max. length via Outdoor (M-NET cable) L1+L2+L3+L4, L1+L2+L6+L7, L3+L4+L6+L7 <=500m[1640ft.] 1.25mm
Max. length to Outdoor (M-NET cable) L1, L3+L4, L6, L2+L6, L7
Max. length from MA to Indoor
OC
(51)
TB3
M1
M2
TB7
M1
M2
S
Shielded wire
OC
(54 )
TB7
M1 M2 S
TB3
M1
Power Supply Unit
PAC-SC51KUA
A B
S
AT-50A
A B
S
OC: Outdoor unit controller; IC: Indoor unit controller; MA: MA remote controller
2-1-2. Using ME Remote controller
Long transmission cable causes voltage down, therefore, the length limitation should be obeyed to secure proper transmission.
Max. length via Outdoor (M-NET cable) L1+L2+L3+L4, L1+L2+L6+L7,L1+L2+L3+L5, L3+L4+L6+L7 <=500m[1640ft.] 1.25mm
Max. length to Outdoor (M-NET cable)
Max. length from ME to Indoor
*1. If the length from ME to Indoor exceed 10m, use 1.25 mm
OC
(51)
TB3
M1
M2
TB7
M1
M2
S
Shielded wire
OC
(54 )
TB7
M1 M2 S
TB3
M1
Power Supply Unit
PAC-SC51KUA
A B
S
AT-50A
A B
S
OC: Outdoor unit controller; IC: Indoor unit controller; ME: ME remote controller
a1+a2, a1+a2+a3+a4
Group1
IC
(01)
TB5
TB15
M1 M2
S
1 2
A B
MA
L
3
IC
(02)
TB5
TB15
M2
M1 M2 S
1 2
V+V-FG
L1, L3+L4, L6, L2+L6, L7, L3+L5
e1, e2+e3, e4
2
[AWG16] shielded cable, but the total length should be counted into Max. length via Outdoor.
Group1
IC
(01)
TB5
M1 M2 S
A B
(101)
ME
L
3
IC
(02)
TB5
M1 M2 S
M2
V+V-FG
SYSTEM DESIGN
<=200m[656ft.]
<=200m[656ft.]
L
1
Group3
IC
IC
(04)
(05)
TB5
TB15
TB5
TB15
M1 M2 S
1 2
M1 M2 S
1 2
A B
MA
L
4
IC
IC
(03)
(07)
TB 15
TB5
TB5
TB15
M1 M2 S
1 2
M1 M2 S
1 2
A B
MA
<=200m[656ft.]
<=10m[32ft.]*1
L
1
Group3
IC
IC
(04)
(05)
TB5
TB5
M1 M2 S
M1 M2 S
A B
(105)
ME
L
4
IC
IC
(03)
(07)
TB5
TB5
M1 M2 S
M1 M2 S
A B
(103)
ME
C7-R Rev.
2
[AWG16] or thicker
2
1.25mm
[AWG16] or thicker
2
0.3-1.25 mm
[AWG22-16]
Group5
IC
(06)
TB5
TB15
M1 M2 S
1 2
a2
a4
A B
MA
2
[AWG16] or thicker
2
1.25mm
[AWG16] or thicker
2
0.3-1.25 mm
[AWG22-16] *1
Group5
IC
(06)
TB5
M1 M2 S
e3
A B
(155)
ME
4 - 41

Advertisement

Table of Contents
loading

Table of Contents