Have all electrical work performed by an authorized electri- Only use accessories (i.e., air cleaners, humidifiers, electric cian according to the local regulations and the instructions heaters) recommended by Mitsubishi Electric. in this manual. Use a dedicated circuit. Insufficient power supply capacity or improper installation of the unit may result in malfunctions of the unit, electric shock, or fire.
Page 3
When installing the unit in a small space, take appropriate mended by Mitsubishi Electric may result in smoke, fire, or precautions to prevent leaked refrigerant from reaching the explosion.
CONTENTS I Features [1] Features............................ 1 II Components and Functions [1] Components and Functions...................... 2 III Specfications [1] Specifications..........................4 1.Specfications .......................... 4 2.Electrical component specifications..................7 IV Outlines and Dimensions [1] Outlines and Dimensions......................8 [2] Service Space......................... 10 V Wiring Diagram [1] Wiring Diagram ........................
[ II Components and Functions ] II Components and Functions [1] Components and Functions 1. Indoor (Main) Unit (1) In case of rear inlet (2) In case of bottom inlet Air inlet Air inlet Air outlet Air outlet 2. Remote Controller [PAR-21MAA] Once the operation mode is selected, the unit will remain in the selected mode until changed.
Page 8
[ II Components and Functions ] (2) Remote Controller Display Current time/Timer time Louver swing Centralized control indicator Ventilation Timer OFF indicator Filter sign Timer mode indicator Sensor position Operation mode display: COOL, DRY, AUTO, Room temperature FAN, HEAT Function mode indicator Vane setting Preset temperature Fan speed...
[ IV Outlines and Dimensions ] IV Outlines and Dimensions [1] Outlines and Dimensions 1. PEFY-P20, 25, 32, 40, 50, 63, 71, 80, 100, 125, 140VMA-E Note 1 Use M10 suspension bolts. (not supplied) 2 Provide an access door for maintenance at the bottom. 3 The dimensions in the table are those of the PEFY-P63, 71, 80, 100, 125, 140VMA-E models, which have 2 fans.
Page 14
[ IV Outlines and Dimensions ] 2. PEFY-P20, 25, 32, 40, 50, 63, 71, 80, 100, 125, 140VMAL-E Note 1 Use M10 suspension bolts. (not supplied) 2 Provide an access door for maintenance at the bottom. 3 The dimensions in the table are those of the PEFY-P63, 71, 80, 100, 125, 140VMAL-E models, which have 2 fans.
[ IV Outlines and Dimensions ] [2] Service Space PEFY-P20, 25, 32, 40, 50, 63, 71, 80, 100, 125, 140VMA(L)-E Secure enough access space to allow for the maintenance, inspection, and replacement of the motor, fan, drain pump, heat exchanger, and electric box in one of the following ways. Select an installation site for the indoor unit so that its maintenance access space will not be obstructed by beams or other objects.
[ VI Refrigerant System Diagram ] VI Refrigerant System Diagram [1] Refrigerant system diagram Gas pipe thermistor TH23 Gas pipe Liquid pipe Brazed connections Strainer (#100 mesh) Linear expansion valve Liquid pipe thermistor TH22 Heat exchanger Room temperature thermistor TH21 Capacity PEFY- PEFY-...
[ VII Troubleshooting ] VII Troubleshooting [1] Troubleshooting 1. Check methods 1. Component and check points (1) Thermistor Room temperature thermistor (TH21) Liquid pipe thermistor (TH22) Gas pipe thermistor (TH23) Disconnect the connector and measure the resistance between terminals with a tester. (Ambient temperature 10°C - 30°C) Normal Abnormal...
Page 20
[ VII Troubleshooting ] 1) Summary of linear expansion valve (LEV) operation The LEV is operated by a stepping motor, which operates by receiving a pulse signal from the indoor control board. The LEV position changes in response to the pulse signal. Indoor control board and LEV connection 12VDC Brown...
Page 21
[ VII Troubleshooting ] 2) LEV operation Close Open Fully open valve (2000 pulses) No. of pulses Extra tightning (80 - 100 pulse) Valve opening degree When the power is turned on, a pulse signal of 2200 pulses is output (valve closure signal), to bring the valve to position A. When the valve is operating normally, it is free of vibration noise.
Page 22
[ VII Troubleshooting ] Symptom Checking Criteria Remedy Valve closure fail- To check the LEV on the indoor unit, check the indoor unit liquid pipe temperature Replace the LEV ure (leaky valve) that appears on the operation monitor on the outdoor unit's multi control board while if the amount of operating the indoor unit in question in the FAN mode and the other indoor units in leakage is great.
[ VII Troubleshooting ] 2. DC fan motor (fan motor/indoor control board) 1. CAUTION A high voltage is applied to the connector for connection to the fan motor (CNMF). Do not unplug the connector CNMF with the unit energized to avoid damage to the indoor control board and fan motor. 2.
[ VII Troubleshooting ] 3. Address switch setting Make sure that power to the unit is turned off. Please see the WIRING LABEL on the control box. Indoor unit control board Factory setting 1. When using an ME remote controller, set the address with the rotary switches (SW11, SW12). Address setting is not required when the unit remote controller is used.
[ VII Troubleshooting ] 5. Dipswitch setting (Factory setting) 1. Function setting (1) SW1 Switch position Function Switch setting Active Thermistor (Intake air Built-in thermistor on the remote Indoor unit thermistor) controller Filter clogging detection Available Unavailable Filter life 2500 hr 100 hr Outdoor air intake Enabled...
Page 27
[ VII Troubleshooting ] 2. Capacity code setting (1) SW2 1) Indoor control board Dipswitch settings must be made while the unit is stopped. Factory setting The switches are set to correspond to the unit capacity. PEFY-P20VMA(L)-E PEFY-P25VMA(L)-E PEFY-P32VMA(L)-E PEFY-P40VMA(L)-E PEFY-P50VMA(L)-E PEFY-P63VMA(L)-E PEFY-P71VMA(L)-E...
Page 28
[ VII Troubleshooting ] 5. External static pressure (1) SWA, SWC 1) Indoor control board All models Factory 35Pa 50Pa 70Pa 100Pa 150Pa setting SWA SWC Note: Changes that are made to the dipswitches SWA and SWC immediately become effective regardless of the unit's operation status (RUN/STOP) or the remote controller status (ON/OFF).
[ VIII Disassembly Procedure ] VIII Disassembly Procedure [1] Disassembly Procedure 1. Control box Exercise caution when removing heavy parts. 1. Removing the control box cover (1) Remove the three fixing screws on the cover (A) to re- move it. Fig.1 Fig.2 - 24 -...
[ VIII Disassembly Procedure ] 2. Thermistor (Intake air) Exercise caution when removing heavy parts. 1. Remove the control box cover according to the procedure in section [1]. 2. Remove the thermistor. (1) Pull out the thermistor holder (B) and thermistor (C) on the control box.
[ VIII Disassembly Procedure ] 3. Drainpan Exercise caution when removing heavy parts. 1. Removing the filter and the bottom plate (1) Push down the tab on the filter, and pull out the filter in the direction of the arrow 1. (2) Remove the fixing screws on the bottom plate (D), (E) to remove it.
[ VIII Disassembly Procedure ] 4. Thermistor (Gas pipe) (Liquid pipe) Exercise caution when removing heavy parts. 1. Remove the drain pan according to the procedure in sec- tion [1]. 2. Removing the Heat exchanger cover (1) Remove the four fixing screws on the heat exchanger cov- er (F) to remove it.
[ VIII Disassembly Procedure ] 5. Fan and fan motor Exercise caution when removing heavy parts. 1. Removing the filter and the bottom plate (1) Push down the tab on the filter, and pull out the filter in the direction of the arrow 1. (2) Remove the fixing screws on the bottom plate (J) to re- move it.
[ VIII Disassembly Procedure ] 6. Heat exchanger Exercise caution when removing heavy parts. 1. Remove the drain pan according to the procedure in section [1]. 2. Remove the heat exchanger cover according to the proce- dure in section [4] 2. 3.
Page 36
http://Global.MitsubishiElectric.com New publication effective Sep. 2012 Specifications subject to change without notice HWE0812B...