2. EXTERNAL DIMENSIONS

2. EXTERNAL DIMENSIONS
PLFY-P32, 40, 50, 63, 80, 100, 125VBM-E-S
20~45
Fresh air
Suspension bolt pitch
160
intake hole
Transmission terminal block
Power supply
Branch duct hole
terminal block
Suspension bolt
187.5
M10 or W3/8
1
60
284
2
*
*
Suspension bolt
lower edge
Power supply wire,
*
Indoor unit/Outdoor unit
connecting wire entry
Control wire entry
Air intake hole
M
Air intake
grille
M
Air outlet hole
Indoor unit
Ceiling
3000 mm or
more
Grille
Obstacle
1500 mm
or more
Ceiling hole
860~910
20~45
810
For MA-Remote controller
terminal block
160
840
Drain pipe
PVC pipe: O.D. 32 (1-1/4")
377
*
*
*
Ceiling
Grille
597
Drain hole
Drain pump clean hole
and Drain emergency
drainage hole
M
Auto vane
(Air outlet)
M
Vane motor
500
83
36
950
Indoor unit
1800mm or more
from floor
For high
attachment
Floor
INDOOR UNITS
Detail connecting of Branch duct(Both aspects)
Ø175
Branch duct hole
Burring hole pitch
(
Connected the attached
flexible pipe or socket.
I.D. 32 (1-1/4")
Keep approximatety
10 to 15 mm space
between unit ceilling
and ceilling slab.
*
In case of standard grille : PLP-6BA-S
In case of Auto-Grille : PLP-6BAJ-S
In case of wireless remote controller : PAR-FL32MA
Emergency operation switch<Cooling>
and Emergency Up/Down switch<Up>
Emergency operation
switch<Heating>and
Emergency Up/Down switch<Down>
DEFROST/STAND BY lamp
Receiver
Operation lamp
Note 1. Please choose the Grille from a standard grille, Auto-Grille.
2. As for drain pipe, please use VP-25(O.D. Ø32 PVC TUBE).
Drain pump inclusion.
Raise is max 850mm from the ceiling.
3. As for suspension bolt, please use M10 or W3/8. (Procured at local site)
4. Electrical box may be removed for the service purpose.
Make sure to slack the electrical wire little bit for control/power wires connection.
5. The height of the indoor unit is able to be adjusted with the grille attached.
6. For the installation of the optional high efficiency filter or optional
multi-functional casement.
1) Requires E or more space between transom and ceiling for the installation.
2) Add 135 mm to the dimensions * marked on the figure.
3) The optional high efficiency filter becomes optional multi-functional
casement and concomitant use.
7. When installing the branch ducts, be sure to insulate adequately.
Otherwise condensation and dripping may occur.
(It becomes the cause of dew drops/Wear dew.)
8. As for necessary installation/service space, please refer to the left at figure.
Accessory ··· Drain socket (I.D. 32 (1-1/4"))
1
Models
Refrigerant pipe···Ø6.35
PLFY-P32,40,50VBM-E-S
Flared connection···1/4inch
PLFY-P63,80VBM-E-S
Refrigerant pipe···Ø9.52
Flared connection···3/8inch
PLFY-P100,125VBM-E-S
C7-R Rev.
unit : mm
90
100
100
90
Cut out hole
350
14-Ø2.8
Burring hole
Ø150
Cut out hole
Detail drawing of fresh air intake hole
Burring hole
3-Ø2.8
Burring hole pitch
Ø125
)
Cut out hole
Ø100
*
Ceiling
Auto-Grille
Air intake grille Up/down distance
L.L Filter
Air intake grille
2
A
B
C
D
E
Refrigerant pipe ···
Ø
12.7
80
74
Flared connection···1/2inch
400
241 258
Refrigerant pipe···
Ø
15.88
85
77
Flared connection···5/8inch
281
298
440
*
Ceiling
1 - 80