Connecting to Condensate Drain
A significant amount of condensate will form due to the
cooling of the air that passes through the heat exchanger.
The condensate drain from the supply and the extract air
side of the unit is fitted with hoses that can be looped to
form a condensate watertrap. The end of the hose will have
to be connected to a floor gully or a drainage system.
To ensure proper operation of the Combi unit, ensure that
the the two watertraps hold at lease 100 mm watercolum.
Ensure that the hose drops at least 1 % downward to the
drain to ensure sufficient draining of condensate.
Depending on air humidity, the amount of condensate
formed can reach 1 l/h.