Temperature Regulators For Cooling Applications - Samson 43-3 Mounting And Operating Instructions

Table of Contents

Advertisement

8.1.2

Temperature regulators for cooling applications

Malfunction
Possible reasons
Seat and plug are worn or leak.
Foreign particles blocking the plug
Sensor installed in the wrong location.
Sensor installed incorrectly.
Temperature at the
sensor exceeds the
set point.
Regulator or K
Incorrectly installed valve
Insufficient cooling energy available
Control thermostat defective
Mixing valve: port A closed
Diverting valve: port B closed.
Strainer blocked.
Regulator or K
Temperature at the
Sensor installed in the wrong location.
sensor fluctuates.
Sensor installed incorrectly.
Time constant is too large for the control
loop.
Slow control
response
Sensor installed incorrectly.
EB 2173 EN
/C
coefficient too small
VS
V
/C
coefficient too large
VS
V
Recommended action
Î Clean the seat and plug.
Î Contact SAMSON's After-sales Service.
Î Remove foreign particles.
Î Contact SAMSON's After-sales Service.
Î Change the mounting position.
Î Immerse the temperature sensor with its entire
immersion depth in the process medium.
Î Avoid an installation site where idle times or
heat buildup can occur.
Î Check the sizing.
Î Install a suitable valve.
Î Contact SAMSON's After-sales Service.
Î During installation, observe the correct
direction of flow and arrangement of the ports
A/B/AB.
Î Draw up an energy balance.
Î Replace the control thermostat.
Î Clean the strainer.
Î Check the sizing.
Î Install a suitable valve.
Î Contact SAMSON's After-sales Service.
Î Change the mounting position.
Î Immerse the temperature sensor with its entire
immersion depth in the process medium.
Î Avoid an installation site where idle times or
heat buildup can occur.
Î Fill the thermowell with thermal paste or
remove the thermowell.
Î Use a sensor with smaller time constant (e.g.
vapor pressure thermostat).
Î Immerse the temperature sensor with its entire
immersion depth in the process medium.
Î Avoid an installation site where idle times or
heat buildup can occur.