6.5
Four-Wire Smoke Detector Wiring
FIRE ALARM MAIN BOARD
+
-
RESETTABLE 4-WIRE SMOKE
DETECTOR POWER SUPPLY
22VDC, 200mA
MAX. CURRENT - 300mA
MAX. RIPPLE VOL. 5mV
(POWER LIMITED)
LEGEND
3.9K 1/2 WATT ELR
Figure 18 Four-wire smoke detector wiring - class B
6.6
Relay Adder Module Wiring
Wire relays on the relay adder module MR-2306-R6 as shown in Figure 19.
Figure 19 Relay per zone (MR-2306-R6) terminal connection
+
+
POWER
-
-
+
+
-
-
DETECTION
4-WIRE DETECTION DEVICE
TO INITIATING
CIRCUIT
5
6
2
3
1
4
END OF LINE RELAY
LISTED S3403
MODEL A77-716B
MANUFACTURED BY
SYSTEM SENSOR
NOTES
ALL POWER LIMITED CIRCUITS
MUST USE TYPE FPL, FPLR,
OR FPLP POWER LIMITED
CABLE
27