Safety Precautions - Thermo Scientific WAE 32-OSD Operating Instructions Manual

Barnstead softening system
Table of Contents

Advertisement

5. Safety precautions

Observe these safety precautions for your own safety!
The exclusive purpose of your WAE 32/60-OSD softening system is to soften drinking
water.
Do not start to install or operate the system until you have taken notice of the
appropriate information given in these operating instructions.
Two people are required to lift and carry the softening system (to the installation
location, for example). Take hold of it at the corner points under the base plate.
Please note that the manufacturer is not liable for damages resulting from a use other
than the intended purpose or improper operation.
The CE-Mark is invalidated when constructional changes are made to the system or
products from other manufacturers are installed in it.
Protect the system from frost. The temperature in the area in which the system is
installed must be at least +2° C and is not to exceed +40° C.
Observe all applicable general regulations and requirements that apply at the
installation area, including accident prevention regulations.
The raw water pressure must be at least 2 bar and not more than 6 bar. If the raw
water pressure is higher, install an additional pressure reducing valve.
Water purification systems must be equipped with a safety device acc. to DIN EN
1717 to protect the tap water line from contamination.
A 230V, 50Hz socket with a protective contact must be made available.
The installation area must have a free running floor-level drain of at least DN 50 (38.5
internal diameter). When such a drain is not available, we recommend that you install
a water watcher (article no. 16.0129), otherwise the manufacturer will not accept any
liability for damage caused by water.
Gravity flow to the waste water system is to be ensured.
Position the system so that operation of the voltage network separation device is not
impaired.
Ensure that there will be sufficient working room around the system for unproblematic
operation of it when selecting the installation area.
The warranty is valid for a period of 12 months.
8
Thermo Scientific Barnstead
Softening system WAE 32/60-OSD

Advertisement

Table of Contents
loading

This manual is also suitable for:

Wae 60-osd5014019350140235

Table of Contents