Field Settings for Indoor Unit
1.4.40 Access Permission Level Setting
For BRC1E73 only
There are 2 levels as follows:
1.4.41 Setback Availability
For BRC1E73 only
Select the operation mode in which the setback function is available.
Mode
1.4.42 Setting "Restricted/Permitted" for Airflow Block
For units with the infrared presence/floor sensor only
The airflow block function cannot be enabled when closure material kit, fresh air intake kit,
separately installed natural evaporation type humidifier, or branch air duct is equipped, due to the
possibility of dew condensation.
This setting restricts the airflow block function, preventing that the airflow block is inadvertently set
to ON.
Ensure that "Airflow block restricted" is set when using the options listed above.
Mode
213
Level 2: The following buttons are selectable to be disable or enable.
Level 3: No buttons are selectable and only On/Off button is available.
Button
On/Off
Mode
Fan Speed
Menu/OK
Cancel
Mode No.
First Code No.
1c
3
First Code
Second Code
No.
No.
No.
01
02
1e
2
03
04
First Code
Second Code
No.
No.
No.
01
02
1e
14
03
04
05
Level 2
Selectable (Enable)
Selectable (Enable)
Selectable (Enable)
Selectable (Disable)
Unselectable (Disable)
Unselectable (Disable)
Second Code No.
01
02
Contents
N/A
Heat only
Cool only
Cool/heat
Contents
Airflow block permitted
Airflow block restricted
Part 5 Field Settings and Test Operation
SiUS372201EA
Level 3
Unselectable (Disable)
Unselectable (Enable)
Unselectable (Disable)
Unselectable (Disable)
Unselectable (Disable)
Unselectable (Disable)
( ) shows the factory setting.
: Factory setting
Contents
Level 2
Level 3
: Factory setting
: Factory setting
—
—
—