Daikin REYQ-AATJA Service Manual page 169

Table of Contents

Advertisement

SiUS372201EA
9.2.2 With Infrared Floor Sensor
The relationship between remote controller set temperature and control target temperature is
described below.
 The temperature difference for cooling  heating mode switching is 5°C (9°F).
 When using the floor temperature as the control target, the remote controller set
 The above also applies to automatic operation.
 When setting the suction air thermistor (Default setting)
 When using the remote controller thermistor (Field setting is required)
Examples are given to illustrate a control target temperature that satisfies the remote controller set
temperature.
Regarding control target temperature
When using the infrared floor sensor, the temperature around people will be treated as the control
target temperature for operation.
What is the temperature around people?
The temperature around people refers to the temperature of the living space, obtained from the
temperature around the ceiling and the temperature underfoot. The temperature is calculated using
the detected values of the suction air thermistor and the infrared floor sensor.
It is difficult to use only suction air temperature control for underfoot air conditioning.
Part 4 Functions and Control
temperature is equal to the actual control target temperature in heating operation.
Temperature
Remote controller set temperature
Cooling
Control target temperature
Remote controller set temperature
Heating
Control target temperature
Temperature
Remote controller set temperature
Cooling
Control target temperature
Remote controller set temperature
Heating
Control target temperature
Outline of Control (Indoor Unit)
14 15
16 17 18 19
20 21 22
23 24 25 26
27 28
57.2
59
60.8
62.6
64.4
66.2
68
69.8
71.6
73.4
75.2
77
78.8 80.6 82.4 84.2
14 15
16 17 18 19
20 21 22
23 24 25 26
27 28
57.2
59
60.8
62.6
64.4
66.2
68
69.8
71.6
73.4
75.2
77
78.8 80.6 82.4 84.2
29
30
31 32 33 34
35 36˚C
86
87.8
89.6 91.4 93.2
95
96.8
˚F
29
30
31 32 33 34
35 36˚C
86
87.8
89.6 91.4 93.2
95
96.8
˚F
162

Advertisement

Table of Contents
loading

This manual is also suitable for:

Reyq-aayda

Table of Contents