Troubleshooting by Error Code

3. Troubleshooting by Error Code
3.1

Error Codes and Descriptions

Error
Operation
code
lamp
A0
A1
A3
A6
A7 (1)
k
A8
A9
AA
AF (1)
k
Indoor
AH
Unit
AJ
C1
C4
C5
C6
C9 (2)
CA
CC
k
CE (1)
k
CJ (2)
k
E1
E2
E3
E4
E5
E6
E7
Outdoor
Unit
E9
EA
F3
K k  l
F4
F6
Branch
Selector
F9
Unit
275
External protection device abnormality
l
Indoor unit control PCB abnormality
l
l
Drain level control system abnormality
Indoor fan motor lock, overload
Indoor fan motor abnormality
Overload/overcurrent/lock of indoor fan motor
l
Blower motor not running
Indoor fan motor status abnormality
Low indoor airflow
Swing flap motor abnormality
Power supply voltage abnormality
l
Blower motor stops for over/under voltage
l
Electronic expansion valve coil abnormality, dust clogging
Gas furnace abnormality
l
Drain level above limit
l
Self-cleaning decoration panel abnormality
l
Capacity determination device abnormality
Transmission abnormality between indoor unit control PCB and fan PCB
l
Blower motor communication error
Climate Talk communication error
l
Indoor heat exchanger liquid pipe thermistor abnormality
Indoor heat exchanger gas pipe thermistor abnormality
l
Combination error between indoor unit control PCB and fan PCB
l
Blower motor HP mismatch
Indoor blower does not have required parameters to function
Suction air thermistor abnormality
l
Remote sensor abnormality
l
Discharge air thermistor abnormality
Humidity sensor system abnormality
Infrared presence/floor sensor error
Remote controller thermistor abnormality
l
Outdoor unit main/sub PCB abnormality
Detection of ground leakage by leak detection circuit
l
Missing of ground leakage detection core
Activation of high pressure switch
l
l
Activation of low pressure sensor
l
Compressor motor lock
l
Compressor damage alarm
Outdoor fan motor abnormality
l
Electronic expansion valve coil abnormality
l
Sub PCB momentary overcurrent
Four way valve abnormality (intermediate stop)
Four way valve abnormality (not switching)
l
Opposite air conditioning alarm
l
Discharge pipe temperature abnormality
Wet alarm
Refrigerant overcharged
l
l
Branch Selector unit electronic expansion valve abnormality
Error contents
SiUS372201EA
k: ON h: OFF l: Blink
Reference
page
291
293
294
296
298
302
303
304
305
306
308
309
310
311
312
313
324
325
327
328
329
329
330
331
332
329
333
329
334
335
340
341
342
343
344
346
347
349
351
353
353
354
355
357
358
360
362
363
Part 6 Service Diagnosis