GEM eSyStep 543 Operating Instructions Manual page 52

Motorized angle seat globe valve
Table of Contents

Advertisement

12 Specific data IO-Link (pin 6)
12.4.20 Function digital in- / output 1
The function of the input/output can be set with the Function Digital In-/Output 1 (subindex 1) parameter.
Index Sub-
Off-
Access
In-
set
Rights
dex
0x4C
1
0
R/W
2
8
R/W
Description of parameter values
Index name
Function digital in- /
output 1
GEMÜ 543 eSyStep
OPEN / CLOSE (Code AE)
Length
Index name
3 bits
Function digital
in- / output 1
3 bits
Parameter
Values
In- / output
Type in- / output
Parameter
Type
In- / output 1
uint:8
Type in- / output 1
uint:8
0
(Output Open) Signal is output with the corresponding valve
position. Detection of Open depends on the setting of the
parameter Position Feedback (index 0x51 (see "Actuator po-
sition feedback", page 56)) and a correct initialization.
1
(Output Close) Signal is output with the corresponding valve
position. Detection of Close depends on the setting of the
parameter Position Feedback (index 0x51 (see "Actuator po-
sition feedback", page 56)) and a correct initialization.
2
(Output Error) Only output error detection.
3
(Output Error & Warning) Output error and warnings.
4
(Input Init) Configure input/output as initialization input.
0
(Push-Pull) Configure output as Push-Pull.
1
(NPN) Configure output as NPN.
2
(PNP) Configure output as PNP.
52 / 68
Default
Values
4
0
1
2
3
4
0
0
1
2
Description
www.gemu-group.com

Advertisement

Table of Contents
loading

Table of Contents