Fault Status Codes - Prosense Safevader Series User Manual

Table of Contents

Advertisement

8-
Remove main PCB from PCB holder via releasing the latches.
9-
Remove Display module cable from main PCB via unlatching the connector.
10-
Safely locate the display cable in to main hole located on main PCB.
11-
Install new display module cable to main PCB display connector.
12-
Install sensor module in to sensor connections on main PCB.
13-
Fix main pcb to enclosure cover.
14-
Fix front panel to enclosure body.
15-
Power On and check status.

Fault Status Codes:

Fault Message
SENSOR
Sensor is in fault condition
ADC
ADC circuit is not functioning correctly
CURRENT
Detector is not generating analogue output signal
POWER
Power input is out of range
CPU RAM
RAM fault detected
CPU FLASH
Flash error detected
EEPROM
EEPROM error detected
CAL DUE
Defined calibration period is passed, calibraton needed
RS485
RS485 communication failure
CPU
CPU failure
TEST DUE
Defined test period is passed, test execution needed
LINE
Analogue output is not connected or shortcircuited
TEMPERATURE
Sensor temperature error
NO COMM
Display communication failure
PRS-UM-SV-EN-Rev1.0-16.12.2022
Fault Description
Table 7: SAFEVADER Series Fault Status Codes