Default Configuration - Prosense Safevader Series User Manual

Table of Contents

Advertisement

Default Configuration:

Function
Value/Setting
Sensor Type
Automatic detection
2mA (1.0 - 3.5 mA adjustable)
3mA (1.0 - 3.5 mA adjustable)
3mA (1.0 – 4.0 mA adjustable)
3mA (1.0 – 4.0 mA adjustable)
Signal output
4.0 mA to 20.0 mA
22mA (20.0 - 22.0 mA adjustable)
2mA (1.0 - 3.5 mA - adjustable)
Value is sensor dependant
Alarm Relay
De-energized
1*
Contact Normally Open (NO)
Value is sensor dependant
Alarm Relay
De-energized
2*
Contact Normally Open (NO)
Value is sensor dependant
Fault Relay
Energized
Contact Normally Open (NO)
Password
Gas Name
Range
Oxygen
25.0%vol
Toxic
1-1000ppm
VOC
100-1000ppm
Refrigerant gases 2000-10000ppm
Flammable
100%LEL
5%Vol
Carbon Dioxide
5000ppm
PRS-UM-SV-EN-Rev1.0-16.12.2022
Table 11: SAFEVADER Series default Configuration
Detector Default Alarm Settings
Lower
Alarm
19%Vol
%10 of FS Rising
%10 of FS Rising
%10 of FS Rising
10%LEL
1%Vol
2000ppm Rising
Table 12: SAFEVADER Series default alarm settings
Meaning
SAFEVADER automatically detect the sensor
Fault
Warm-Up
Inhibit
Calibration mode
Normal gas measurement
Over range
Under range (Fault)
Lower alarm level
Energizes on alarm
Closes on alarm
Higher alarm level
Energizes on alarm
Closes on alarm
Detector Fault
De-energizes on alarm
Closes on alarm
1234 password to menu access
Lower Alarm Type Higher Alarm
Falling
23%vol
%15 of FS
%15 of FS
%15 of FS
Rising
15%LEL
Rising
2%Vol
3000ppm
Higher Alarm
Type
Rising
Rising
Rising
Rising
Rising
Rising
Rising
Page 39 / 41