Display Parameters; Change Language; Change Zero Suppression - Prosense Safevader Series User Manual

Table of Contents

Advertisement

User can adjust these values to desired values depending of the application requirements
between 1 to 3.5 mA for Fault, Warm-up, Calibration, Inhibit and 20-22mA for Overrange.

Display Parameters

Detector display can be adjusted as per requirements. The display options are given in Display
menu item

Change Language

The detector display language can be changed to English or Turkish. To change Language first
select Configure option on main menu then select Display option and Language option. Once
you reach to Language screen you will able to switch display language:

Change Zero Suppression

User can adjust the way showing measurement level around zero level. If zero suppression
mode set to NO, detector will display measurement as detected. If zero suppression mode set
to YES, detector will show measurement levels as 0 (zero) up to 3% LEL. At 3% LEL it will display
measurements as detected.
To change zero suppression mode select Zero Suppression option on Display menu and pres
Enter key. Current zero suppression mode will be displayed. If needed change the value via
using up and down keys. Once adjusted press Enter key to record value.
PRS-UM-SV-EN-Rev1.0-16.12.2022
1. Language
2. Zero Suppression
3. Password
4. Detector model
5. Previous Menu
Menu Language
English
Zero Suppression
NO
Page 26 / 41