Siemens SITRANS F FX330 Operating Instructions Manual page 94

Vortex flowmeters
Table of Contents

Advertisement

OPERATION
6
Status
Event group
type
S
Sensor
S
Electronics
S
Process
S
Config: Totalizer
M
Sensor Information
94
Single event
Flow Meas. Out of Spec.
Low Flow Cutoff Undercut
Weak Flow Meas. Signal
Pres.Sen.Temp. Out of Spec. Temperature of the internal
Elec. Temp. Out Of Spec.
Elec. Temp. Out Of Spec.
CO Undersaturation
CO Oversaturation
Flow Totalizer Overflow
Energy Totalizer Overflow
Faulty Sensor Oscillator
Faulty sensor voltage ref.
www.siemens.com/flow
Description
The vortex frequency or the
volume flow is out of range.
The real flow is higher or
lower than the indicated
value.
Volume flow is lower than
low flow cutoff (LFC)
The vortex signal is too weak
or disturbed.
pressure sensor out of
specification.
The electronic temperature
of the sensor module is out
of specification.
The electronic temperature
of the converter is out of
specification.
The measurement value is
lower than the lower range
value of the current output.
The current output is
saturated and does not
reflect the effective
measuring value.
The measurement value is
higher than the upper range
value of the current output.
The current output is
saturated and does not
reflect the effective
measuring value.
The actual value of the flow
counter exceeds its preset
value.
The actual value of the
energy counter exceeds its
preset value.
The sensor oscillator is
working out of range.
Reference voltage in sensor
module out of specification.
SITRANS FX330
Actions to eliminate the
event
Check the process
conditions.
Check the low flow cut-off or
the process conditions.
Check the process
conditions and the
installation situation.
Eliminate external
disturbances. If the
message recurs, contact the
manufacturer.
Make sure that the device is
operated within the
permissible temperature
range.
Make sure that the device is
operated within the
permissible temperature
range.
Check the process
conditions and the lower
current output limit.
Check the process
conditions and the upper
current output limit.
Check the setting of the flow
counter or reset the counter.
The actual value of the
energy counter exceeds its
preset value.
Perform a hard reset. If the
message recurs, contact the
manufacturer.
05/2019 - A5E36751269-AE