Security recommendations
3.1 Security recommendations
• Ensure that the latest firmware version is installed, including all security-related patches.
You can find the latest information on security patches for Siemens products at the Industrial
Security (https://www.siemens.com/industrialsecurity) or ProductCERT Security Advisories
(https://www.siemens.com/cert/en/cert-security-advisories.htm) website.
For updates on Siemens product security advisories, subscribe to the RSS feed on the
ProductCERT Security Advisories website or follow @ProductCert on Twitter.
• Enable only those services that are used on the device, including physical ports. Free physical
ports can potentially be used to gain access to the network behind the device.
• Use the authentication and encryption mechanisms of SNMPv3 if possible. Use strong
passwords.
• Configuration files can be downloaded from the device. Ensure that configuration files are
adequately protected.
Configuration files can be password protected during download. You enter passwords on the
WBM page "System > Load & Save > Passwords".
• When using SNMP (Simple Network Management Protocol):
– Configure SNMP to generate a notification when authentication errors occur.
– Ensure that the default community strings are changed to unique values.
– Use SNMPv3 whenever possible. SNMPv1 and SNMPv2c are considered non-secure and
– If possible, prevent write access.
Interfaces security
• Disable unused interfaces.
• Use IEEE 802.1X for interface authentication.
• Use the function "Locked Ports" to block interfaces for unknown nodes.
• Use the configuration options of the interfaces, e.g. the "Edge Type".
• Configure the receive ports so that they discard all untagged frames ("Tagged Frames Only").