OPERATION

Firmware Upgrade

By upgrading the Firmware, you can obtain new features
and updates/improvements to existing functionality. To
ensure the frmware is kept up to date, please regularly
visit our website to see if there is any updated frmware
version available. There are three methods for upgrading
the PDU frmware. Please follow the instructions below for
the method that is appropriate for your application. There
are two fles to update in order to upgrade the frmware
version:
• cpsmpdumafw_XXX.bin
• cpsmpdumadata_XXX.bin
Note that the XXX is not part of the fle name but is where
the version number in the flename is given.
Prior to performing a frmware update, please:
• Download the latest frmware from
www.cyberpower.com.
• Extract the downloaded frmware fle to your local
"C:\" drive.
Note:
1. The FTP service needs to be enabled before attempting
to execute a frmware upgrade.
2. Please do not turn the PDU of when performing the
frmware upgrade. PDU outlets will remain powered on
while the frmware update takes place. Only the PDU
LCD screen will reboot.
3. The PDU LCD screen will reboot during the frmware
update process. This DOES NOT cause the PDU outlets
to reboot.
Option 1: Single Device Upgrade
Use the following steps to upgrade the frmware.
1. Open a command prompt window and navigate to "C:\".
2. Login to the PDU with FTP command, type
- C:\>ftp
- ftp> open 192.168.22.126 21
(for example: 192.168.22.126 is the current IP of the
PDU and 21 is the default ftp port for the PDU)
- Connected to 192.168.22.126.
- 220 CyberPower FTP Server Ready.
- User (192.168.22.126:(none)):cyber
- 331 User name okay, need password.
- Password:
- 230 User logged in, proceed.
- ftp>
3. Upload the cpsmpdumafw_XXX.bin, type
- ftp > bin
- ftp > put cpsmpdumafw_XXX.bin
4. Upgrade complete, type
- ftp > quit
5. The system will reboot after you type "quit". This reboot
will take approximately 30 seconds.
6. Login to the PDU via FTP again, type
- C:\>ftp
- ftp> open 192.168.22.126 21
(for example: 192.168.22.126 is the current IP of the
PDU and 21 is the default ftp port for the PDU)
- Connected to 192.168.22.126.
- 220 CyberPower FTP Server Ready.
- User (192.168.22.126:(none)):cyber
- 331 User name okay, need password.
- Password:
- 230 User logged in, proceed.
- ftp>
7. Upload cpsmpdumadata_XXX.bin, type
- ftp > bin
- ftp > put cpsmpdumadata_XXX.bin
8. Upgrade complete, type
- ftp > quit
9. The system will reboot after you type "quit".
Note: You can check to see if the frmware upgrade is
successful by checking the "Firmware version" on the
[System->About] screen via web UI.
Option 2: Single or Multiple Device Upgrade
(recommended)
Use the following steps to upgrade the frmware.
1. Download the Upgrade and Confguration Utility from
www.cyberpower.com.
2. Open Upgrade and Confguration Utility from
Start > All Programs >
CyberPower Upgrade and Confguration Utility.
3. Wait for search to fnish (Figure 1).
28
Figure 1