Danfoss VLT HVAC Drive FC 102 Operating Instructions Manual page 96

Low harmonic drive
Hide thumbs Also See for VLT HVAC Drive FC 102:
Table of Contents

Advertisement

Specifications
Control characteristics
Resolution of output frequency at 0–1000 Hz
System response time (terminals 18, 19, 27, 29, 32, 33)
Speed control range (open-loop)
Speed accuracy (open-loop)
All control characteristics are based on a 4-pole asynchronous motor
Surroundings
Enclosure, frame size D and E
Enclosure, frame size F
Vibration test
Relative humidity
Aggressive environment (IEC 60068-2-43) H
Test method according to IEC 60068-2-43 H
Ambient temperature (at 60 AVM switching mode)
- with derating
- with full output power, typical EFF2 motors (see )
- at full continuous FC output current
1)
8
8
For more information on derating, consult the design guide
Minimum ambient temperature during full-scale operation
Minimum ambient temperature at reduced performance
Temperature during storage/transport
Maximum altitude above sea level without derating
Maximum altitude above sea level with derating
For more information on derating, consult the design guide
EMC standards, emission
EMC standards, immunity
Control card performance
Scan interval
Control card, USB serial communication
USB standard
USB plug
NOTICE!
Connection to PC is carried out via a standard host/device USB cable.
The USB connection is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
The USB connection is not galvanically isolated from ground protection. Use only isolated laptop/PC as connection to
the USB connector on the adjustable frequency drive or an isolated USB cable/drive.
Protection and Features:
Electronic thermal motor protection against overload.
Temperature monitoring of the heatsink ensures that the adjustable frequency drive trips if the temperature
reaches a predefined level. An overload temperature cannot be reset until the temperature of the heatsink is below
the allowed values.
The adjustable frequency drive is protected against short-circuits on motor terminals U, V, W.
If a line phase is missing, the adjustable frequency drive trips or issues a warning (depending on the load).
Monitoring of the intermediate circuit voltage ensures that the adjustable frequency drive trips if the intermediate
circuit voltage is too low or too high.
94
®
VLT
HVAC Drive FC 102 Low Harmonic Drive
5–95% IEC 721-3-3; Class 3K3 (non-condensing) during operation
S test
2
S (10 days)
2
EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6
Danfoss A/S © 04/2015 All rights reserved.
1:100 of synchronous speed
30–4000 RPM: Maximum error of ±8 RPM
-13°–+149°/158°F [-25°–+65°/70°C]
EN 61800-3, EN 61000-6-3/4, EN 55011, IEC 61800-3
EN 61800-3, EN 61000-6-1/2,
USB type B device plug
±0.003 Hz
≤ 2 ms
IP21, IP54
IP21, IP54
0.7 g
class kD
1)
max. 131°F [55°C]
1)
max. 122°F [50°C]
1)
max. 113°F [45°C]
32°F [0°C]
14°F [-10°C]
3300 ft [1,000 m]
10,000 ft [3000 m]
5 ms
1.1 (full speed)
MG16I322