Application Examples
6.2.4 RS485
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
6
6
D IN
37
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
01
02
03
04
05
06
61
68
69
Table 6.9 RS485 Network Connection
64
®
VLT
HVAC Drive FC 102 Low Harmonic Drive
Parameters
Function
Setting
Parameter 8-30
Protocol
FC*
Parameter 8-31
1*
Address
Parameter 8-32
9600*
Baud Rate
* = Default value
Notes/comments:
Select protocol, address and
Baud rate in the parameters
mentioned above.
D IN 37 is an option.
RS-485
+
-
Danfoss A/S © 04/2015 All rights reserved.
6.2.5 Motor Thermistor
WARNING
THERMISTOR INSULATION
Risk of personal injury or equipment damage.
Use only thermistors with reinforced or double
insulation to meet PELV insulation
requirements.
VLT
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
U - I
A53
Table 6.10 Motor Thermistor
Parameters
Function
Setting
Parameter 1-90
[2]
Motor Thermal
Thermistor
Protection
trip
Parameter 1-93 T
[1] Analog
hermistor Source
input 53
* = Default Value
Notes/comments:
If only a warning is desired,
parameter 1-90 Motor Thermal
Protection should be set to [1]
Thermistor warning.
D IN 37 is an option.