Electrical Installation

4.11 F-frame Options

Space heaters and thermostat
There are space heaters mounted on the cabinet interior of
F-frame frequency converters. These heaters are controlled
by an automatic thermostat and help control humidity
inside the enclosure. The thermostat default settings turn
on the heaters at 10 °C (50 °F) and turn them off at
15.6 °C (60 °F).
Cabinet light with power outlet
A light mounted on the cabinet interior of F-frame
frequency converters increases visibility during servicing
and maintenance. The housing includes a power outlet for
temporarily powering tools or other devices, available in 2
voltages:
230 V, 50 Hz, 2.5 A, CE/ENEC
120 V, 60 Hz, 5 A, UL/cUL
Transformer tap set-up
If the cabinet light, outlet, and/or the space heaters, and
thermostat are installed, transformer T1 requires its taps to
be set to the proper input voltage. A 380–480/500 V
frequency converter is initially set to the 525 V tap, to
ensure that no overvoltage of secondary equipment occurs
if the tap is not changed before applying power. See
Table 4.15 to set the proper tap at terminal T1 located in
the rectifier cabinet.
Input voltage range [V]
380–440
441–500
Table 4.15 Transformer Tap Set-up
NAMUR terminals
NAMUR is an international association of automation
technology users in the process industries, primarily
chemical and pharmaceutical industries in Germany.
Selecting this option, provides terminals organised and
labeled to the specifications of the NAMUR standard for
frequency converters input and output terminals. This
®
requires VLT
PTC Thermistor Card MCB 112 VLT
Extended Relay Card MCB 113.
RCD (residual current device)
Uses the core balance method to monitor ground fault
currents in grounded and high-resistance grounded
systems (TN and TT systems in IEC terminology). There is a
pre-warning (50% of main alarm set-point) and a main
alarm set-point. Associated with each set-point is an SPDT
alarm relay for external use. Requires an external window-
type current transformer (supplied and installed by the
customer).
MG16I322
Operating Instructions
Tap to select [V]
400
460
®
and
Danfoss A/S © 04/2015 All rights reserved.
Integrated into the frequency converter safe
torque off circuit.
IEC 60755 Type B device monitors AC, pulsed DC,
and pure DC ground fault currents.
LED bar graph indicator of the ground fault
current level from 10–100% of the setpoint.
Fault memory.
TEST/RESET key.
Insulation resistance monitor (IRM)
Monitors the insulation resistance in ungrounded systems
(IT systems in IEC terminology) between the system phase
conductors and ground. There is an ohmic pre-warning
and a main alarm setpoint for the insulation level. An SPDT
alarm relay for external use is associated with each
setpoint.
NOTICE!
Only 1 insulation resistance monitor can be connected to
each ungrounded (IT) system.
Integrated into the frequency converter Safe
Torque Off circuit.
LCD display of the ohmic value of the insulation
resistance.
Fault memory.
INFO, TEST, and RESET keys.
IEC emergency stop with Pilz safety relay
Includes a redundant 4-wire emergency-stop push button
mounted on the front of the enclosure and a Pilz relay that
monitors it in conjunction with the frequency converter
STO (Safe Torque Off) circuit and the mains contactor
located in the options cabinet.
Manual motor starters
Provide 3-phase power for electric blowers often required
for larger motors. Power for the starters is provided from
the load side of any supplied contactor, circuit breaker, or
disconnect switch. Power is fused before each motor
starter, and is off when the incoming power to the
frequency converters is off. Up to 2 starters are allowed (1
if a 30 A, fuse-protected circuit is ordered), and are
integrated into the frequency converter STO circuit.
Unit features include:
Operation switch (on/off).
Short-circuit and overload protection with test
function.
Manual reset function.