Electrical Installation
NOTICE!
Each repeater functions as a node within the segment in
which it is installed. Each node connected within a given
network must have a unique node address across all
segments.
4
4
Terminate each segment at both ends using either the
termination switch (S801) of the adjustable frequency
drives or a biased termination resistor network. Always use
shielded twisted pair (STP) cable for bus cabling, and
always follow good common installation practice.
Low-impedance ground connection of the shield at every
node is important, including at high frequencies. Thus,
connect a large surface of the shield to ground, for
example, with a cable clamp or a conductive cable
connector. It may be necessary to apply potential-
equalizing cables to maintain the same ground potential
throughout the network - particularly in installations with
long cables.
To prevent impedance mismatch, always use the same
type of cable throughout the entire network. When
connecting a motor to the adjustable frequency drives,
always use shielded motor cable.
Cable
Impedance
Cable length
Table 4.10 Cable Recommendations

4.9.2 Mechanical Brake Control

In hoisting/lowering applications, it is necessary to be
able to control an electro-mechanical brake:
Control the brake using any relay output or
digital output (terminal 27 or 29).
Keep the output closed (voltage-free) as long as
the adjustable frequency drive is unable to
'support' the motor, e.g., due to the load being
too heavy.
Select [32] Mechanical brake control in parameter
group 5-4* Relays for applications with an electro-
mechanical brake.
The brake is released when the motor current
exceeds the preset value in
parameter 2-20 Release Brake Current.
The brake engages when the output frequency is
less than the frequency set in
parameter 2-21 Activate Brake Speed [RPM] or
parameter 2-22 Activate Brake Speed [Hz], only if
46
Shielded twisted pair (STP)
120 Ω
Max. 4000 ft [1200 m] (including drop lines)
Max. 1,650 ft [500 m] station-to-station
Danfoss A/S © 04/2015 All rights reserved.
®
VLT
HVAC Drive FC 102 Low Harmonic Drive
If the adjustable frequency drive is in alarm mode or in an
overvoltage situation, the mechanical brake immediately
cuts in.

4.9.3 Parallel Connection of Motors

The adjustable frequency drive can control several motors
connected in parallel. The total current consumption of the
motors must not exceed the rated output current I
the adjustable frequency drive.
NOTICE!
Installations with cables connected in a common joint as
in Figure 4.16, is only recommended for short cable
lengths.
NOTICE!
When motors are connected in parallel,
parameter 1-29 Automatic Motor Adaptation (AMA) cannot
be used.
NOTICE!
The electronic thermal relay (ETR) of the adjustable
frequency drive cannot be used as motor protection for
the individual motor of systems with motors connected
in parallel. Provide further motor protection with
thermistors in each motor or individual thermal relays.
Circuit breakers are not suitable as protection.
Figure 4.16 Installations with Cables Connected in a Common
Joint
Problems are possible at start and at low RPM values if
motor sizes vary widely. The relatively high ohmic
resistance in the stator of small motors calls for a higher
voltage at start and at low RPM values.