Requirement: Section 120.6(c)7 A‐D "CO sensor shall be:  
A. Certified by the manufacturer to be accurate within plus or minus 
5 percent of measurement. 
B. Factory calibrated. 
C. Certified by the manufacturer to drift no more than 5 percent per 
year. 
D. Certified by the manufacturer to require calibration no more fre‐
quently than once a year. 
 
Solution:  Use Honeywell Analytics E3Point Network Gas Monitor with 
carbon monoxide cartridges. 
 
 
Requirement: Section 120.6(c)7Ei "The CO sensor shall be monitored 
by a control system. If any sensor has not been calibrated according to 
the manufacturer's recommendations within the specified calibration 
period, the sensor has failed." 
 
Solution: Use E3Point carbon monoxide sensors, which require cali‐
bration every 12 months.  Create a event to activate if time since cali‐
bration (TSC) is 12 months.  Configure this event to activate fans and 
the alarm device. 
 
 
 
 
 
 
 
 