The top left portion contains the statistic quantifier (available only for 
Groups) that take only the specified part of the group into the equa‐
tion.  Options available in this field are:   
 
 
Option 
all 
includes all transmitters in the group 
includes the average concentration for the group's trans‐
mean 
mitters 
max 
includes the group's maximum concentration 
min 
includes the group's minimum concentration 
includes at least a quarter of the group's transmitters that 
1/4 
meets set conditions 
includes at least a third of the group's transmitters that 
1/3 
meets set conditions 
includes at least half of the group's transmitters that meets 
1/2 
set conditions 
includes at least two thirds of the group's transmitters that 
2/3 
meets set conditions 
includes at least three quarters of the group's transmitters 
3/4 
that meets set conditions 
at least one or more than one of the group's transmitters 
1 or + 
that meets set conditions 
The transmitter that deviates the most from the average 
concentration reading of a group of transmitters is known 
as an outlier. This quantifier is available only in part num‐
bers AA96DC24‐DLC and AAD96DC24‐DLC‐BIP. Further dia‐
log facilitates specifying the deviation from average re‐
outl 
quired to activate the event and the minimum duration for 
this deviation. For example, it is possible to set the devia‐
tion to 15 ppm and the duration to 30 minutes. This is ex‐
plained further in How to Build a California Title 24 Compli‐
ant System on page 96. 
 
 