 Multiple outdoor unit installation
• Provide at least 250 mm of space between the outdoor units if multiple units are installed.
• When routing the piping from the side of an outdoor unit, provide space for piping.
• No more than 3 units must be installed side by side.
When 4 units or more are arranged in a line, provide the space as shown in the following ex-
ample "When an obstruction in the upper space:".
• When the upper space is open:
When there are obstacles at the rear only.
When there are obstacles at the front and
rear.
• When an obstruction in the upper space:
When there are obstacles at the rear and above.
3-1. Model: AOBH27CMTA
250 or more
300
or more
500 or more
1,500 or more
Max. 300
250 or more
1,500 or more
When there are obstacles at the front only.
250 or more
500 or more
- 42 -
Unit: mm
1,500 or more
Unit: mm
1,500 or more