Advertisement

Quick Links

AIR CONDITIONER
Wall mounted type
DESIGN & TECHNICAL MANUAL
INDOOR
OUTDOOR
ASBG09KMBA
ASBG12KMBA
AOBG09KMCA
AOBG12KMCA
DR_AS180EF_01
2023.01.20

Advertisement

Table of Contents
loading

Summary of Contents for Fujitsu ASBG09KMBA

  • Page 1 AIR CONDITIONER Wall mounted type DESIGN & TECHNICAL MANUAL INDOOR ASBG09KMBA ASBG12KMBA OUTDOOR AOBG09KMCA AOBG12KMCA DR_AS180EF_01 2023.01.20...
  • Page 2 Mobile” is a trademark of FUJITSU GENERAL LIMITED. ™ Google Play is trademark of Google LLC. ® App Store is a service mark of Apple Inc., registered in the U.S. and other countries. Copyright © 2023 Fujitsu General Limited. All rights reserved.
  • Page 3: Table Of Contents

    CONTENTS Part 1. INDOOR UNIT................1 1. Specifications....................2 2. Dimensions....................3 2-1. Models: ASBG09KMBA and ASBG12KMBA ..............3 3. Wiring diagrams ....................5 3-1. Models: ASBG09KMBA and ASBG12KMBA ..............5 4. Capacity table....................6 4-1. Cooling capacity.......................6 4-2. Heating capacity ......................7 5. Fan performance ...................8 5-1. Air velocity distributions....................8 5-2.
  • Page 4 CONTENTS (continued) Part 2. OUTDOOR UNIT..............31 1. Specifications....................32 2. Dimensions....................33 2-1. Models: AOBG09KMCA and AOBG12KMCA ..............33 3. Installation space ..................34 3-1. Models: AOBG09KMCA and AOBG12KMCA ..............34 4. Refrigerant circuit ..................37 4-1. Models: AOBG09KMCA and AOBG12KMCA ..............37 5. Wiring diagrams ..................38 5-1.
  • Page 5: Part 1. Indoor Unit

    Part 1. INDOOR UNIT WALL MOUNTED TYPE: ASBG09KMBA ASBG12KMBA...
  • Page 6: Specifications

    1. Specifications Wall mounted Type Inverter, Heat pump Model name ASBG09KMBA ASBG12KMBA Power supply 220 V~ 60 Hz Power supply intake Outdoor unit Available voltage range 198—242 V 2.64 3.52 Rated Btu/h 9,000 12,000 Cooling 0.5—3.2 0.9—3.8 Min.—Max. Btu/h 1,700—10,900 3,100—13,000...
  • Page 7: Dimensions

    2. Dimensions 2-1. Models: ASBG09KMBA and ASBG12KMBA Unit: mm Outline of indoor unit for pipe inlet Ø65 for pipe inlet Ø65 - 3 - 2-1. Models: ASBG09KMBA and ASBG12KMBA 2. Dimensions...
  • Page 8 ¢ Installation space requirement Provide sufficient installation space for product safety. Unit: mm Outline of unit 25 or more 52 or more 70 or more 130 or more 1,500 or more - 4 - 2-1. Models: ASBG09KMBA and ASBG12KMBA 2. Dimensions...
  • Page 9: Wiring Diagrams

    3. Wiring diagrams 3-1. Models: ASBG09KMBA and ASBG12KMBA - 5 - 3-1. Models: ASBG09KMBA and ASBG12KMBA 3. Wiring diagrams...
  • Page 10: Capacity Table

    Airflow Rate (AFR): For cooling capacity: Total Capacity (TC), Sensible Heat Capacity (SHC), and Input Power (IP) For heating capacity: Total Capacity (TC) and Input Power (IP) 4-1. Cooling capacity ¢ Model: ASBG09KMBA Indoor temperature °CDB °CWB °CDB...
  • Page 11: Heating Capacity

    4-2. Heating capacity ¢ Model: ASBG09KMBA Indoor temperature °CDB °CWB 1.71 0.90 1.71 0.93 1.70 0.93 1.70 0.97 1.69 0.99 2.06 0.95 2.05 0.98 2.04 0.98 2.04 1.02 2.03 1.05 2.40 1.00 2.39 1.02 2.38 1.03 2.38 1.07 2.37 1.10 2.75...
  • Page 12: Fan Performance

    5. Fan performance 5-1. Air velocity distributions ¢ Model: ASBG09KMBA Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Horizontal louver: Up Vertical louver: Center Unit: m/s Top view Horizontal louver: Up Vertical louver: Left & Right Unit: m/s...
  • Page 13 ¢ Model: ASBG12KMBA Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Horizontal louver: Up Vertical louver: Center Unit: m/s Top view Horizontal louver: Up Vertical louver: Left & Right Unit: m/s Side view Horizontal louver: Up Vertical louver: Center Unit: m/s Side view Horizontal louver: Down...
  • Page 14: Airflow

    5-2. Airflow ¢ Model: ASBG09KMBA  Cooling Fan speed Airflow HIGH QUIET  Heating Fan speed Airflow HIGH QUIET - 10 - 5-2. Airflow 5. Fan performance...
  • Page 15 ¢ Model: ASBG12KMBA  Cooling Fan speed Airflow HIGH QUIET  Heating Fan speed Airflow HIGH QUIET - 11 - 5-2. Airflow 5. Fan performance...
  • Page 16: Operation Noise (Sound Pressure)

    6. Operation noise (sound pressure) 6-1. Noise level curve ¢ Model: ASBG09KMBA  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 HIGH HIGH NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 NC-15 NC-15...
  • Page 17: Sound Level Check Point

    6-2. Sound level check point Microphone Microphone NOTE: Detailed shape of the actual indoor unit might be slightly different from the one illustrated above. - 13 - 6-2. Sound level check point 6. Operation noise (sound pressure)
  • Page 18: Safety Devices

    7. Safety devices Model Type of Protection form protection ASBG09KMBA ASBG12KMBA Circuit protection Current fuse (PCB*) 250 V, 3.15 A °C Activate Fan motor stop Fan motor Thermal protector protection program °C Reset Fan motor restart *PCB: Printed Circuit Board - 14 - 7.
  • Page 19: External Input And Output

    8. External input and output With using external input and output functions, this product can be operated inter-connectedly with an external device. Connector Input Output Remarks CNA01 Control input — See external input/output CNB01 — Operation status output settings for details. CNB02 —...
  • Page 20 • When function setting is “Forced stop” mode: Input signal Forced stop Command Normal Operation Indoor unit Stop Remote controller Remote control operation invalidity • Optional part: Part name Model name Exterior External input wire External Connect Kit UTY-XWZXZ5 Communication Kit UTY-XCBXZ2 * For operating the external function, the wall mounted type requires the communication kit in addi- tion to the wire (UTY-XWZXZ5).
  • Page 21: External Output

    8-2. External output With using external output function, operating status of this product can be transmitted to the exter- nal device, and also, this product can be inter-connected with the external device. ¢ Operation status output Air conditioner operation status signal can be output. •...
  • Page 22 ¢ Error status output Air conditioner error status signal can be output. • Circuit diagram example: Indoor unit control PCB Communication kit Connected unit Connector DC 24 V Example: Relay unit Example: Display Relay power supply 10 m* Signal Optional parts Locally purchased –...
  • Page 23: Group Connection

    9. Group connection Wiring regulation on the remote controllers in the multi-split systems are reviewed and allowed for group connection. Example of group connection Indoor unit Indoor unit Outdoor unit Outdoor unit *Exterior of each device shown above might be different from the actual one. NOTES: •...
  • Page 24: Remote Controller Address Setting Procedure For Wireless Remote Controllers

    • Required parts for group connection – Optional part: Indoor unit type Communication Kit Wall mounted UTY-XCBXZ2 As for the optional parts, "Others" on page 30 – Service part: Wire with connector (Service part no. 9705932012) Wiring example for multiple remote control or group control: Crimping terminal and its insulation cap (Locally purchased) Remote controller cable (Locally purchased)
  • Page 25: Remote Controller

    10. Remote controller 10-1. Wireless remote controller ¢ Overview a MODE button b FAN SPEED button c POWERFUL button d 10 °C HEAT button e ECONOMY button f CANCEL button g OUTDOOR LOW NOISE button h ENERGY SAVING button i RESET button j TEST RUN button k SERVICE CHECK button l CLOCK ADJUST button...
  • Page 26 ¢ Specifications  Controller Unit: mm Top view Front view Side view Size (H × W × D) 181 × 58 × 17 Weight 116 (without batteries)  Holder Unit: mm Top view Ø (Hole) Hole 26.3 62.8 Front view Side view Size (H ×...
  • Page 27: Function Settings

    11. Function settings To adjust the functions of this product according to the installation environment, various types of function settings are available. NOTE: Incorrect settings can cause a product malfunction. 11-1. Function settings by using remote controller Some function settings can be changed on the remote controller. After confirming the setting proce- dure and the content of each function setting, select appropriate functions for your installation envi- ronment.
  • Page 28 ¢ Contents of function setting Each function setting listed in this section is adjustable in accordance with the installation environ- ment. NOTE: Setting will not be changed if invalid numbers or setting values are selected.  Function setting list Function no. Functions Remote controller address setting Filter sign...
  • Page 29 2) Filter sign Select appropriate intervals for displaying the filter sign on the indoor unit according to the estimated amount of dust in the air of the room. If the indication is not required, select "No indication" (03). Function number Setting value Setting description Factory setting...
  • Page 30 7) Remote controller custom code (Only for wireless remote controller) The indoor unit custom code can be changed. Select the appropriate custom code. Function number Setting value Setting description Factory setting ♦ 8) External input control "Operation/Stop" mode or "Forced stop" mode can be selected. Function number Setting value Setting description...
  • Page 31: 11-2.Custom Code Setting For Wireless Remote Controller

    11-2. Custom code setting for wireless remote controller To interconnect the air conditioner and the wireless remote controller, assignment of the custom code for the wireless remote controller is required. NOTE: Air conditioner cannot receive a signal if the air conditioner has not been set for the custom code.
  • Page 32: Accessories

    12. Accessories 12-1. Models: ASBG09KMBA and ASBG12KMBA Part name Exterior Part name Exterior Self-tapping screw Operation manual (large) Self-tapping screw Installation manual (small) Wall hook bracket Filter holder Remote controller Ion deodorization filter Remote controller Apple-catechin filter holder Cloth tape - 28 - 12-1.
  • Page 33: Optional Parts

    13. Optional parts 13-1. Controllers Exterior Part name Model name Summary Large and full-dot liquid crystal screen, wide and large keys easy to press, user-intuitive arrow key. Wired Remote Wire type: Polar 3-wire UTY-RVNYM Controller Optional Communication Kit is necessary for installation. Room temperature can be controlled by detecting the temperature accurately with thermo sensor.
  • Page 34: 13-2.Others

    13-2. Others Exterior Part name Model name Summary Required when external device is connected. External UTY-XWZXZ5 Connect Kit Use to connect with optional devices Communication UTY-XCBXZ2 and air conditioner PCB. Remotely manage an air conditioning system using mobile devices such as smartphones and tablets.
  • Page 35: Part 2. Outdoor Unit

    Part 2. OUTDOOR UNIT SINGLE TYPE: AOBG09KMCA AOBG12KMCA...
  • Page 36: Specifications

    1. Specifications Type Inverter, Heat pump Model name AOBG09KMCA AOBG12KMCA Power supply 220 V~ 60 Hz Available voltage range 198—242 V Starting current Cooling 1,650 1,700 Airflow rate Heating 1,650 1,450 Type × Qty Propeller fan × 1 Motor output Cooling Sound pressure level* dB (A)
  • Page 37: Dimensions

    2. Dimensions 2-1. Models: AOBG09KMCA and AOBG12KMCA Unit: mm 4-M10 hole Pitch of bolts for installation Top view Side view Front view Side view Airflow Drain port Ø42 Bottom view Side view (Valve part) - 33 - 2-1. Models: AOBG09KMCA and AOBG12KMCA 2.
  • Page 38: Installation Space

    3. Installation space 3-1. Models: AOBG09KMCA and AOBG12KMCA ¢ Space requirement Provide sufficient installation space for product safety. CAUTION Keep the space shown in the installation examples. If the installation is not performed accordingly, it could cause a short circuit and result in a lack of operating performance.
  • Page 39  Multiple outdoor unit installation • Provide at least 250 mm of space between the outdoor units if multiple units are installed. • When routing the piping from the side of an outdoor unit, provide space for piping. • No more than 3 units must be installed side by side. When 4 units or more are arranged in a line, provide the space as shown in the following ex- ample “When an obstruction in the upper space:”.
  • Page 40  Outdoor units installation in multi-row Unit: mm Single parallel unit arrangement Multiple parallel unit arrangement 100 or more 200 or more 1,000 or more 2,000 or more 200 or more 400 or more 500 or more 1,000 or more 200 or more 250 or more 1,000 or more...
  • Page 41: Refrigerant Circuit

    4. Refrigerant circuit 4-1. Models: AOBG09KMCA and AOBG12KMCA Heat exchanger 3-way (INDOOR) valve 2-way Muffler valve 4-way valve Strainer Expansion valve Heat exchanger Strainer (OUTDOOR) Cooling Heating : Thermistor (Discharge temperature) : Thermistor (Outdoor temperature) : Thermistor (Heat exchanger out temperature) : Thermistor (Pipe temperature) : Thermistor (Room temperature) - 37 -...
  • Page 42: Wiring Diagrams

    5. Wiring diagrams 5-1. Models: AOBG09KMCA and AOBG12KMCA - 38 - 5-1. Models: AOBG09KMCA and AOBG12KMCA 5. Wiring diagrams...
  • Page 43: Capacity Compensation Rate For Pipe Length And Height Difference

    6. Capacity compensation rate for pipe length and height difference Height difference H Indoor unit is higher than outdoor unit Indoor unit is lower than outdoor unit Outdoor unit Indoor unit Outdoor unit Indoor unit Connection pipe Connection pipe 6-1. Model: AOBG09KMCA NOTE: Values mentioned in the table are calculated based on the maximum capacity.
  • Page 44: Model: Aobg12Kmca

    6-2. Model: AOBG12KMCA NOTE: Values mentioned in the table are calculated based on the maximum capacity. Pipe length (m) COOLING — — — 0.858 0.868 — — 0.929 0.872 0.882 Indoor unit is higher than outdoor unit *1 — 0.960 0.933 0.876 0.885...
  • Page 45: Additional Charge Calculation

    7. Additional charge calculation 7-1. Model: AOBG09KMCA Refrigerant type Factory charge amount ¢ Refrigerant charge Total pipe length 15 or less 20 (Max.) 20 g/m Additional charge amount 7-2. Model: AOBG12KMCA Refrigerant type Factory charge amount ¢ Refrigerant charge Total pipe length 15 or less 20 (Max.) 20 g/m...
  • Page 46: Airflow

    8. Airflow 8-1. AOBG09KMCA  Cooling 1,650  Heating 1,650 8-2. AOBG12KMCA  Cooling 1,700 1,001  Heating 1,450 - 42 - 8-1. AOBG09KMCA 8. Airflow...
  • Page 47: Operation Noise (Sound Pressure)

    9. Operation noise (sound pressure) 9-1. Noise level curve ¢ AOBG09KMCA  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000...
  • Page 48: Sound Level Check Point

    9-2. Sound level check point Rear Microphone Microphone Airflow Side view Rear view NOTE: Detailed shape of the actual outdoor unit might be slightly different from the one illustrated above. - 44 - 9-2. Sound level check point 9. Operation noise (sound pressure)
  • Page 49: Electrical Characteristics

    10. Electrical characteristics Model name AOBG09KMCA AOBG12KMCA Voltage Power supply Frequency Maximum operating current* Starting current Circuit breaker current Power cable 1.0—1.5 Wiring Cross-sectional spec.* Connection area cable* Limited wiring length NOTES: • * : Maximum operating current is the total current of the indoor unit and the outdoor unit. •...
  • Page 50: Safety Devices

    11. Safety devices Model Type of Protection form protection AOBG09KMCA AOBG12KMCA 250 V, 20 A Circuit Current fuse (PCB*) protection 250 V, 5 A 103 ±18°C Activate Fan motor stop Fan motor Thermal protection protection 95 ±18°C Reset Fan motor restart 110°C Activate Compressor stop...
  • Page 51: Accessories

    12. Accessories 12-1. Models: AOBG09KMCA and AOBG12KMCA Part name Exterior Part name Exterior Installation manual Drain pipe - 47 - 12-1. Models: AOBG09KMCA and AOBG12KMCA 12. Accessories...

This manual is also suitable for:

Asbg12kmbaAobg09kmcaAobg12kmca

Table of Contents